Huawei UPS5000-S-600 kVA User Manual page 155

Singapore, threephase, three-wire
Hide thumbs Also See for UPS5000-S-600 kVA:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Singapore, Three-phase, Three-wire)
Item
THDi
Table 8-5 Bypass input electrical specifications
Item
Input system
Rated input voltage
Rated frequency
Input frequency
Input system
For details about the battery parameters, see the
Table 8-6 Battery specifications
Item
Battery management
Cold start
Charger output
power
Batteries with no
neutral wire
Table 8-7 Output electrical specifications
Item
Output system
Issue 01 (2021-04-14)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Specifications
● THDi ≤ 3% (full linear load)
● THDi ≤ 5% (full non-linear load)
Specifications
Three-phase, three-wire, and PE; does not support Δ-
type transformer input; supports only Y-type transformer
input
380 V AC/400 V AC/415 V AC/420 V AC/480 V AC (line
voltage)
50 Hz or 60 Hz
±6 Hz (0.5–6 Hz, ±2 Hz by default)
The mains input and bypass input can share a power
source or use different power sources.
Specifications
Intelligent battery management
If a mains outage occurs, batteries can start the UPS to
supply power to loads.
Under rated conditions, the maximum charge power of
a module is 15 kW.
Supported
Specifications
Three-phase, three-wire, and PE
8 Technical Specifications
SmartLi 2.0 User Manual .
147