11.9 No RS485 Communication

A communication error can be detected when monitoring the special relays for serial
communication.
Make sure the transmission cables have been securely connected between the two
(+) terminals and the two (-) terminals of the stations.
Make sure the characteristics of the transmission cables are within the specified
ranges. See "Transmission Cables" on page 94.
Make sure all of the cables in the link are of the same type.
Make sure the terminating resistors have been correctly set on the first and on the last
station only.
Check that link areas do not overlap.
When using FPG-COM4:
When the RS485 port (COM port 1) of FPG-COM4 is used, set the baud rate in the system
registers to either 19200bit/s or 115200bit/s. Set DIP switch SW1-2 of the cassette to the
same setting (see page 162).