Transmission Cables - Panasonic FPS Series User Manual

Table of Contents

Advertisement

Installation and Wiring

6.7.1 Transmission Cables

Please use the following cables for systems using RS485 type communication cassettes.
Type
Shielded twisted pair
4
3
VCTF
3
Cover
1
Insulator
2
Conductor
3
Shield
4
NOTE
Only use shielded twisted pair cables.
Only use one type of transmission cable. Do not mix more than one type.
Twisted pair cables are recommended in noisy environments.
When using shielded cable with crossover wiring for the RS485
transmission line, ground one end.
If two wires are connected to the plus and minus terminals of the RS485
port of FPG-COM4, use wires of the same cross-sectional area (0.5–
0.75mm
94
Conductor
Size
2
[mm
]
≥1.25
(AWG16)
1
≥0.5
2
(AWG20)
1
≥0.75
(AWG18)
2
2
).
Resistance (at
Material
20°C) [Ω/km]
≤16.8
Polyethylene
≤33.4
Polychlorinated
≤25.1
biphenyl
FPΣ User's Manual
Insulator
Thickness
[mm]
≤0.5
≤0.5
≤0.6
Cable
diameter
[mm]
≈8.5
≈7.8
≈6.6

Advertisement