F166_Highspeedcounter_Set, Target Value Match On - Panasonic FPS Series User Manual

Table of Contents

Advertisement

High-Speed Counter and Pulse Output
System variables for memory areas used:
Description
High-speed counter: elapsed
value of channel
REFERENCE
Please refer to the FPWIN Pro online help for programming examples.

7.3.4.3 F166_HighSpeedCounter_Set, Target Value Match ON

If the elapsed value of the high-speed counter matches the target value, an interrupt process
immediately turns the specified output to TRUE.
Characteristics of target value match ON control
10000
0
2
3
4
10000
Target value
Elapsed value of high-speed counter
1
Execution condition
2
High-speed counter control flag
3
PLC output
4
The PLC output turns to TRUE when the elapsed value matches the target value. In addition, the high-speed counter
control flag turns to FALSE and the instruction is deactivated.
REFERENCE
Please refer to the FPWIN Pro online help for details and a programming
example.
114
System variable
0
sys_diHscChannel0ElapsedValue
1
sys_diHscChannel1ElapsedValue
2
sys_diHscChannel2ElapsedValue
3
sys_diHscChannel3ElapsedValue
1
FPΣ User's Manual
Address
DDT90044
DDT90048
DDT90200
DDT90204