1:1 Communication - Panasonic FPS Series User Manual

Table of Contents

Advertisement

FPΣ User's Manual
When sending data, operation is as follows:
F159_MTRN is executed to send data to the external device. When F159_MTRN is executed:
1. The "transmission done" flag turns to FALSE.
2. The start code is sent automatically.
3. The number of bytes to be sent is set in offset 0 of the send buffer.
4. The characters a and b are sent to the external device.
- The end code is automatically added to the data sent.
- While F159_MTRN is being executed, no data can be received. (The
"transmission done" flag is FALSE.)
5. When the specified number of bytes has been sent, the "transmission done" flag turns
to TRUE.
6. Now, F159_MTRN can be executed again. When F159_MTRN is executed:
- Steps 1 to 5 are repeated. This time, the characters c, d, and e are sent.

8.6.6 1:1 Communication

This section describes 1:1 program controlled communication in which the FPΣ acts as a
master. The examples below contain the wiring diagrams for the connection to a Micro-
Imagechecker and to another FP series PLC.
System register settings
By default, the COM port is set to MEWTOCOL-COM mode. For 1:1 program controlled
communication, the system registers should be set as shown below.
Settings for TOOL port
No.
Name
412
TOOL port - communication mode
413
TOOL port - communication format
415
TOOL port - baud rate
420
TOOL port - receive buffer starting address
421
TOOL port - receive buffer capacity
8.6 Program Controlled Communication
Set value
Program controlled
Data length:
7 bits/8 bits
Parity:
None/Odd/Even
Stop bit:
1 bit/2 bits
End code:
CR/CR+LF/None/ETX
Start code:
No STX/STX
2400–115200bit/s
0–32762 (initial value: 0)
0–2048 words (initial value: 0 words)
203