Configuring The Ma Output - Emerson Micro-Motion 2400S Configuration And Use Manual

Transmitters with analog outputs
Table of Contents

Advertisement

Required Transmitter Configuration
Table 6-7
Pressure measurement units continued
Display
ProLink II
MPA
megapascals
TORR
Torr
ATM
atms
6.5

Configuring the mA output

The Model 2400S AN transmitter has one mA output. Table 6-8 lists the parameters that must be set
for the mA output, and shows the names used for each parameter by the display, ProLink II, and the
Communicator.
Table 6-8
mA output configuration parameters
ProLink II
Primary variable
Lower range value
Upper range value
AO cutoff
AO added damp
AO fault action
AO fault level
To configure the mA output, see the menu flowcharts in Figure 6-5. For details on mA output
parameters, see Sections 6.5.1 through 6.5.4.
Note: If you use the display to configure the mA output, you can configure only the process variable
and the range. To configure other mA output parameters, use ProLink II or the Communicator.
Figure 6-5
Configuring the mA output
ProLink II
ProLink >
Configuration
Analog output
44
Pressure unit
Communicator
MPa
torr
@ 0C
atms
Communicator
PV
PV LRV
PV URV
PV AO cutoff
PV AO added damp
AO1 fault indicator
mA1 fault value
On-Line Menu >
1 Channel setup
4 AO setup
Unit description
Megapascals
Torr @ 0 °C
Atmospheres
Parameter name
Communicator
5 Detailed Setup
3 Config outputs
®
Micro Motion
Model 2400S Transmitters with Analog Outputs
Display
SRC
4 MA
20 MA
Not applicable
Not applicable
Not applicable
Not applicable
Display
Off-line maint >
Off-line config
IO
CH A