Emerson Micro-Motion 2400S Configuration And Use Manual page 147

Transmitters with analog outputs
Table of Contents

Advertisement

Troubleshooting
Table 11-4
Status alarms and remedies continued
Communicator
Alarm
code
ProLink II
A009
Transmitter
Initializing/Warming
Up
Transmitter
Initializing/Warming
Up
A010
Calibration Failure
Calibration Failure
A011
Excess Calibration
Correction, Zero
too Low
Zero Too Low
A012
Excess Calibration
Correction, Zero
too High
Zero Too High
A013
Process too Noisy
to Perform Auto
Zero
Zero Too Noisy
A014
Transmitter Failed
Transmitter Failed
A016
Line RTD
Temperature
Out-Of-Range
Line RTD
Temperature
Out-of-Range
A017
Meter RTD
Temperature
Out-Of-Range
Meter RTD
Temperature
Out-of-Range
A020
Calibration Factors
Unentered
Calibration Factors
Unentered
(FlowCal)
Configuration and Use Manual
Cause
Transmitter in power-up
mode.
Mechanical zero: The
resulting zero was greater
than 3 μs.
Temperature/Density Cals:
many possible causes.
See A10
See A10
See A10.
Many possible causes.
The value computed for
the resistance of the Line
RTD is outside limits
The value computed for
the resistance of the
Meter/Case RTD is
outside limits
The flow calibration factor
and/or K1 has not been
entered since the last
master reset.
Suggested remedy
• Allow the flowmeter to warm up (approximately 30
seconds). The error should disappear once the
flowmeter is ready for normal operation.
• If alarm does not clear, make sure that the sensor is
completely full or completely empty.
• Check the sensor circuitry. See Section 11.25.
• If alarm appears during a transmitter zero, ensure
that there is no flow through the sensor, then retry.
• Cycle power to the flowmeter, then retry.
• If appropriate, restore the factory zero to return the
flowmeter to operation.
• Ensure that there is no flow through the sensor, then
retry.
• Cycle power to the flowmeter, then retry.
• If appropriate, restore the factory zero to return the
flowmeter to operation.
• Ensure that there is no flow through the sensor, then
retry.
• Cycle power to the flowmeter, then retry.
• If appropriate, restore the factory zero to return the
flowmeter to operation.
• Remove or reduce sources of electromechanical
noise, then retry. Sources of noise include:
- Mechanical pumps
- Pipe stress at sensor
- Electrical interference
- Vibration effects from nearby machinery
• Cycle power to the flowmeter, then retry.
• If appropriate, restore the factory zero to return the
flowmeter to operation.
• Cycle power to the flowmeter.
• The transmitter might need service. Contact Micro
Motion. See Section 11.3.
• Check the sensor RTD circuitry. See Section 11.25.
• Verify that process temperature is within range of
sensor and transmitter.
• If the problem persists, contact Micro Motion. See
Section 11.3.
• Check the sensor RTD circuitry. See Section 11.25.
• Verify that process temperature is within range of
sensor and transmitter.
• If the problem persists, contact Micro Motion. See
Section 11.3.
• Check the characterization. Specifically, verify the
FCF and K1 values. See Section 6.2.
• Check the characterization. Specifically, verify the
FCF and K1 values. See Section 6.2.
• If the problem persists, contact Micro Motion. See
Section 11.3.
139