• FQXSPPW0031J: Numeric sensor [NumericSensorElementName] going low (lower non-critical) has
asserted.
This message is for the use case when an implementation has detected a Lower Non-critical sensor going
low has asserted.
Severity: Warning
Serviceable: Yes
Automatically notify Support: No
Alert Category: Warning - Voltage
SNMP Trap ID: 13
CIM Prefix: PLAT CIM ID: 0476
User Action:
CMOS battery is recommended to replace with new one.
Service Action:
Complete the following steps until the problem is solved:
1. Review PD Steps.
2. Replace the system CMOS battery.
3. If problem persists, escalate to next level of support.
• FQXSPPW0035M: Numeric sensor [NumericSensorElementName] going low (lower critical) has
asserted.
This message is for the use case when an implementation has detected a Lower Critical sensor going low
has asserted.
Severity: Error
Serviceable: Yes
Automatically notify Support: Yes
Alert Category: Critical - Voltage
SNMP Trap ID: 1
CIM Prefix: PLAT CIM ID: 0480
User Action:
Complete the following steps:
1. If the specified sensor is Planar 3.3V or Planar 5V, (trained technician only)replace the system board.
2. If the specified sensor is Planar 12V, ensure PDB board is installed correcly and check the XClarity
Controller event log for power-supply-related issues, and resolve those issues.
3. If the problem remains, replace (trained technician only)the PDB board or system board.
124