Connect the analog output wiring to the screw terminals on the Zone Ctrl II and to the controlled device.
Gnd
Any AO
7
Insert the power screw terminal connector into the Zone Ctrl II's power terminals.

Wiring devices to the Zone Ctrl II's Rnet port

The Rnet communicates at a rate of 115 kbps and should be wired in a daisy-chain or hybrid configuration.
Supports up to
5 wireless and/or ZS sensors
One Equipment Touch
One TruVu™ ET Display
For more detailed instructions, see the device's Installation Guide.
CAUTION Rnet power
The Rnet port provides 12 Vdc/200 mA* maximum at 32°F (25°C). that can be used to power zone sensors. If
the total power required by the sensors on the Rnet exceeds the power supplied by the port, use an external
power supply. See the sensor's Installation and Start-up Guide to determine the power required.
* These numbers will be reduced at higher temperatures.

Wiring specifications

Cable from sensor to controller:
Maximum length:
Zone Ctrl II and
VAV Zone II Secondary Duct Installation and Start-up Guide
Error! No text of specified style in document.
0-10 V
+
If <100 ft (30.5 meters)
If >100 ft (30.5 meters)
500 feet (152 meters)
19
Installing the Zone Ctrl II
22 AWG, unshielded
22 AWG, shielded
CARRIER CORPORATION ©2019