Virtual Services Platform 9012 chassis
Value

Virtual Services Platform 9012 placement in the rack

If you place each Virtual Services Platform 9012 in a row from left to right, the chassis to the left
discharges hot air into the cool intake of the chassis to the right.
To optimize airflow, stagger each chassis in racks and add a baffle that redirects hot air discharged
by a chassis from the side to the hot aisle at the back.
Note:
Before setting up your data center plan airflow of cool air into each chassis.
Figure 16: Arrangement of VSP 9012 in rack to optimize airflow
October 2015
FRONT IO-FAN 1 (1-8)
FRONT IO-FAN 2 (1-8)
REAR SF-FAN 1 (1-2)
REAR SF-FAN 2 (1-2)
Installing the Avaya VSP 9000
Comments on this document? infodev@avaya.com
Description
Specifies the status of each of the
fans in the first cooling module.
Specifies the status of each of the
fans in the first cooling module.
Specifies the status of each of the
fans in the rear cooling module.
Specifies the status of each of the
fans in the rear cooling module.