Power And Cooling Requirements; Cs700 Platform - Avaya CS700 Installing Instructions

Audio conferencing server. meeting exchange 4.1
Table of Contents

Advertisement

Power and Cooling Requirements

The following sections describe the thermal and power requirements for each platform.

CS700 Platform

The CS700 can be configured with up to four power supplies that work in tandem to provide a
total of 600W output with N+1 redundancy. The supplies are accessible from the front of the unit
and may be hot swapped.
Thermal Dissipation
The thermal dissipation for the CS700 Platform is less than 1130 BTU per hour.
Input Requirements for AC Systems
The CS700 has two independent AC inputs and can support redundancy. For redundant
operation, connect each input to isolated AC inputs. Systems equipped with four power supplies
will continue to operate normally if one of the AC inputs fails.
Input
Voltage
Range
100 to 240
VAC
The system circuit breaker is rated at 5 A. The breaker is a four-pole device to keep the line and
neutral of each of the two main circuits isolated.
Input
Input Current
Frequency
Range
50 to 60 Hz
Environmental Requirements
Typical input current
(fully-loaded system):
3.8 A @ 115 VAC
Maximum possible
continuous input
current:
5 A @ 115 VAC
Single Cycle Surge
Maximum: <40 A
Power
Factor
>.99
(Supplies
power
factor
corrected)
Issue 1 July 2006