To Insulate The Water Piping - Daikin Altherma 3 M Installer's Reference Manual

Hide thumbs Also See for Altherma 3 M:
Table of Contents

Advertisement

8
|
Piping installation

8.2.7 To insulate the water piping

Installer reference guide
86
The piping in the complete water circuit MUST be insulated to prevent
condensation during cooling operation and reduction of the heating and cooling
capacity.
Outdoor water piping insulation
NOTICE
Outside piping. Make sure the outside piping is insulated as instructed to protect
against hazards.
For piping in free air, it is recommended to use the insulation thickness as shown in
below table as a minimum (with λ=0.039 W/mK).
Piping length (m)
<20
20~30
30~40
40~50
For other cases the minimum insulation thickness can be determined using the
Hydronic Piping Calculation tool.
The Hydronic Piping Calculation tool is part of the Heating Solutions Navigator
which can be reached via https://professional.standbyme.daikin.eu.
Please contact your dealer if you have no access to Heating Solutions Navigator.
This recommendation ensures good operation of the unit, however, local
regulations may differ and shall be followed.
Minimum insulation thickness (mm)
19
32
40
50
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06

Advertisement

Table of Contents
loading

Table of Contents