Daikin Altherma 3 M Installer's Reference Manual page 205

Hide thumbs Also See for Altherma 3 M:
Table of Contents

Advertisement

EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
#
[9.9.5]
[5-06]
[9.9.6]
[5-07]
[9.9.7]
[5-08]
Limit when [9.9.1]=Continuous and [9.9.2]=kW:
#
[9.9.8]
[5-09]
Limits when [9.9.1]=Inputs and [9.9.2]=kW:
#
[9.9.9]
[5-09]
[9.9.A]
[5-0A]
[9.9.B]
[5-0B]
[9.9.C]
[5-0C]
Priority heater
#
[9.9.D]
[4-01]
Note: In case power consumption control is DISABLED (for all models) the setting
[4‑01] defines whether backup heater and booster heater can operate
simultaneously, or if the booster heater/backup heater has priority over the
backup heater/booster heater.
In case power consumption control is ENABLED, the setting [4‑01] defines the
priority of the electrical heaters depending on applicable limitation.
Code
Limit 2: 0 A~50 A
Limit 3: 0 A~50 A
Limit 4: 0 A~50 A
Code
Limit: Only applicable in case of full time
power limitation mode.
0 kW~20 kW
Code
Limit 1: 0 kW~20 kW
Limit 2: 0 kW~20 kW
Limit 3: 0 kW~20 kW
Limit 4: 0 kW~20 kW
Code
Power consumption control DISABLED
[4‑08]=0
0 None : Backup heater and booster heater
can operate simultaneously.
1 Booster heater: The booster heater is
prioritised.
2 Backup
prioritised.
Power consumption control ENABLED
[4‑08]=1/2
0 None : Depending on the power limitation
level, the booster heater will be limited first,
before the backup heater is limited.
1 Booster
power limitation level, the backup heater will
be limited first, before the booster heater is
limited.
2 Backup heater: Depending on the power
limitation level, the booster heater will be
limited first, before the backup heater is
limited.
11
Configuration
|
Description
Description
Description
Description
heater: The backup heater is
heater: Depending on the
Installer reference guide
205