Configuration

11.6.5 Space heating/cooling

Installer reference guide
168
#
Code
[3.A]
[C‑06]
Leaving water temperature: Delta T
For more information, see
#
Code
[3.B.1]
[1-0C]
[3.B.2]
[1-0E]
Overview
The following items are listed in the submenu:
4
Main zone
Additional zone

Space heating/cooling

Tank
User settings
About space operation modes
Your unit can be a heating or a heating/cooling model:
If your unit is a heating model, it can heat up a space.
If your unit is a heating/cooling model, it can both heat up and cool down a
space. You have to tell the system which operation mode to use.
External room thermostat type for the additional
zone:
1: 1
contact. Connected to only 1 digital
input (X2M/35a)
2: 2 contacts. Connected to 2 digital inputs
(X2M/34a and X2M/35a)
4
"Main
zone" [
 154].
Delta T heating: A minimum temperature
difference is required for the good operation of
heat emitters in heating mode.
If [2-0D] = 2, this is fixed to 8°C
Else: 3°C~10°C
Delta T cooling: A minimum temperature
difference is required for the good operation of
heat emitters in cooling mode.
3°C~10°C
[4] Space heating/cooling
[4.1] Operation mode
[4.2] Operation mode schedule
[4.3] Operation range
[4.4] Number of zones
[4.5] Pump operation mode
[4.6] Unit type
[4.7] Pump limitation
[4.9] Pump outside range
[4.A] Increase around 0°C
[4.B] Overshoot
[4.C] Antifrost
Description
Description
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06