9.2.4 External backup heater kit

EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
CAUTION
To guarantee the unit is completely earthed, always connect the backup heater
power supply and the earth cable.
Connect the power supply of the backup heater as follows:
1 Open the service cover. See
2 Connect the power supply cable (including earth) to the appropriate terminals
as shown in the illustration below.
F1B  Overcurrent fuse (field supply). Recommended fuse: 2‑pole; 16 A; curve 400 V;
tripping class C.
Q1DI Earth leakage circuit breaker (field supply)
X6M Terminal (field supply)
3 Fix the cable with cable ties to the cable tie mountings.
For models without integrated backup heater, you can install the external backup
heater kit (EKLBUHCB6W1).
If you do so, then under certain conditions you also need to install a bypass valve
kit (EKMBHBP1).
See:
"To connect the backup heater
"Bypass valve kit
necessity" [
"To connect the bypass valve
"To open the outdoor
X6M
1
F1B
I
2
Q1DI
L
1N~, 50 Hz
230 V AC
X9M
4
kit" [
 102]
4
 106]
4
kit" [
 107]
9
Electrical installation
|
4
unit" [
 72].
3
I
4
N
Installer reference guide
101