Booster heater
Installer reference guide
194
#
Code
[9.3.5]
[6‑04]
Equilibrium
#
Code
[9.3.6]
[5-00]
[9.3.7]
[5-01]
INFORMATION
Above 10°C ambient temperature, the heat pump will operate until 55°C. Configuring
a higher setpoint with an ambient temperature that is higher than the set
equilibrium temperature will prevent the backup heater from assisting. The backup
heater will ONLY assist if you increase the equilibrium temperature [5‑01] to the
required ambient temperature you need to reach the higher setpoint.
Operation
#
Code
[9.3.8]
[4‑00]
Capacity
The capacity of the booster heater must be set for the energy metering and/or
power consumption control feature to work properly. When measuring the
resistance value of the booster heater, you can set the exact heater capacity and
this will lead to more accurate energy data.
#
Code
[9.4.1]
[6‑02]
Description
The capacity difference between the second
and first step of the backup heater at nominal
voltage. Nominal value depends on backup
heater configuration.
Description
Equilibrium: Is backup heater operation
allowed above equilibrium temperature during
space heating operation?
1: NOT allowed
0: Allowed
Equilibrium temperature: Outdoor
temperature below which operation of the
backup heater is allowed.
Range: –15°C~35°C
Description
Backup heater operation:
0: Restricted
1: Allowed
2: Only
DHW: Backup heater operation is
enabled for domestic hot water and disabled
for space heating.
Description
Capacity [kW]. Only applies to domestic hot
water tank with an internal booster heater. The
capacity of the booster heater at nominal
voltage.
Range: 0~10 kW
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06