EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
#
Code
[5.D]
[6-01]
Example: setpoint (T
)>maximum heat pump temperature–[6‑01] (T
U
T
DHW
T
= T
60
U
BUH OFF
T
50
HP MAX
T
48
HP OFF
46
T
HP ON
40
30
20
HP
10
5
BUH Backup heater
HP Heat pump. If heating up time by the heat pump takes too long, auxiliary heating by
the backup heater can take place
T
Backup heater OFF temperature (T
BUH OFF
T
Maximum heat pump temperature at sensor in domestic hot water tank
HP MAX
T
Heat pump OFF temperature (T
HP OFF
T
Heat pump ON temperature (T
HP ON
T
Domestic hot water temperature
DHW
T
User setpoint temperature (as set on the user interface)
U
t Time
Example: setpoint (T
)≤maximum heat pump temperature–[6‑01] (T
U
T
DHW
T
50
HP MAX
T
=T
45
U
HP OFF
T
43
HP ON
40
30
20
HP
10
5
HP Heat pump. If heating up time by the heat pump takes too long, auxiliary heating by
the backup heater can take place
T
Maximum heat pump temperature at sensor in domestic hot water tank
HP MAX
T
Heat pump OFF temperature (T
HP OFF
T
Heat pump ON temperature (T
HP ON
T
Domestic hot water temperature
DHW
T
User setpoint temperature (as set on the user interface)
U
t Time
INFORMATION
The maximum heat pump temperature depends on the ambient temperature. For
more information, see the operation range.
Description
The temperature difference determining the heat
pump OFF temperature.
Range: 0°C~10°C
[6-01]
[6-00]
T
= 60°C
U
T
= 50°C
BUH
HP MAX
[6-01] =
2°C
[6-00] =
2°C
)
U
−[6-01])
HP MAX
−[6-00])
HP OFF
[6-00]
t
−[6-01])
HP MAX
−[6-00])
HP OFF
11
Configuration
|
–[6‑01])
HP MAX
HP
t
–[6‑01])
HP MAX
Installer reference guide