9.2.8 To connect the domestic hot water pump

9.2.9 To connect the alarm output

EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
Wires: (2+GND)×0.75 mm²
DHW pump output. Maximum load: 2 A (inrush), 230 V AC, 1 A
(continuous)
[9.2.2] DHW pump
[9.2.3] DHW pump schedule
1 Open the service cover. See
2 Connect the domestic hot water pump cable to the appropriate terminals as
shown in the illustration below.
X2M
3 Fix the cable with cable ties to the cable tie mountings.
Wires: (2+1)×0.75 mm²
Maximum load: 0.3 A, 250 V AC
[9.D] Alarm output
1 Open the service cover. See
2 Connect the alarm output cable to the appropriate terminals as shown in the
illustration below.
2
1
X2M
7
9
A4P
Y1
YC
"To open the outdoor
X2M.1
M M2P
1~
X2M.2
"To open the outdoor
1+2
Wires connected to the alarm output
3
Wire between X2M and A4P
A4P
Installation of EKRP1HBAA is
required.
3
9
Electrical installation
|
4
unit" [
 72].
4
unit" [
 72].
Installer reference guide