EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
#
Code
[3.5]
[0-00]
[0-01]
[0-02]
[0-03]
Cooling WD curve
Set weather-dependent cooling for the additional zone (if [3.4]=2):
Description
Set weather-dependent heating:
Note: There are 2 methods to set the weather
dependent curve. See
"2-points
and
"Slope-offset
curve" [
types require 4 field settings to be configured
according to the figure below.
T t
[0-01]
[0-00]
[0-03]
[0-02]
T
:
Target
leaving
t
(additional zone)
T
: Outdoor temperature
a
[0-03]: Low outdoor ambient temperature. –
40°C~+5°C
[0-02]: High outdoor ambient temperature.
10°C~25°C
[0-01]: Desired leaving water temperature
when the outdoor temperature equals or drops
below
the
low
[9‑05]°C~[9‑06]°C
Note: This value should be higher than [0‑00]
as for low outdoor temperatures warmer water
is required.
[0-00]: Desired leaving water temperature
when the outdoor temperature equals or rises
above
the
high
[9‑05]~min(45, [9‑06])°C
Note: This value should be lower than [0‑01] as
for high outdoor temperatures less warm water
is required.