Daikin Altherma 3 M Installer's Reference Manual page 70

Hide thumbs Also See for Altherma 3 M:
Table of Contents

Advertisement

7
|
Unit installation
Installer reference guide
70
INFORMATION
If necessary, you can use a drain pan (field supply) to prevent drain water from
dripping.
NOTICE
If the unit CANNOT be installed fully level, always make sure that the inclination is
towards the backside of the unit. This is required to guarantee proper drainage.
NOTICE
If drain holes of the outdoor unit are covered by a mounting base or by floor surface,
raise the unit to provide a free space of more than 150 mm under the outdoor unit.
Drain holes (dimensions in mm)
171
43
48
107
288
451
613
A Discharge side
B Distance between anchor points
C Bottom frame
D Knockout hole for snow
E Drain hole for safety valve
F Drain holes
Snow
In regions with snowfall, snow might build up and freeze between the heat
exchanger and the casing of the unit. This might decrease the operating efficiency.
To prevent this:
1 Remove the knockout hole (a) by tapping on the attachment points with a flat
head screwdriver and a hammer.
A
758
300
148
B
B
C
E
D
F
=
776
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06