Daikin Altherma 3 M Installer's Reference Manual page 212

Hide thumbs Also See for Altherma 3 M:
Table of Contents

Advertisement

11
|
Configuration
Disable protections
Power saving function
Installer reference guide
212
INFORMATION
Protective functions – "Installer-on-site mode". The software is equipped with
protective functions, such as room antifrost. The unit automatically runs these
functions when necessary.
During installation or service this behaviour is undesired. Therefore, the protective
functions can be disabled:
At first power-on: The protective functions are disabled by default. After 36  h
they will be automatically enabled.
Afterwards: An installer can manually disable the protective functions by setting
[9.G]: Disable protections=Yes. After his work is done, he can enable the
protective functions by setting [9.G]: Disable protections=No.
#
Code
[9.G]
N/A
Power saving function
NOTICE
Power saving function. If you want to use the power saving function, on the
compressor module PCB:
Disconnect X804A from X805A.
Connect X804A to X806A.
X806A
3N~
X805A
X805A
1N~
X806A
Defines whether the power supply to the compressor module can be interrupted
(internally by hydro module control) during stand-still conditions (no space
heating/cooling nor domestic hot water demand). The final decision to allow
power interruption of the compressor module during standstill depends on the
ambient temperature, compressor conditions and minimum internal timers.
To enable the power saving function setting, [E‑08] needs to be enabled on the
user interface.
Disable protections:
0: No
1: Yes
X804A
X804A
Description
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06

Advertisement

Table of Contents
loading

Table of Contents