EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
#
Code
[5.8]
[6-0E]
Hysteresis
The following ON hysteresis can be set.
Heat pump ON hysteresis
Applicable when domestic hot water preparation is reheat only. When the tank
temperature drops below the reheat temperature minus the heat pump ON
hysteresis temperature, the tank heats up to the reheat temperature.
The minimum ON temperature is 20°C, even if setpoint hysteresis is smaller than
20°C.
#
Code
[5.9]
[6-00]
Reheat hysteresis
Applicable when domestic hot water preparation is scheduled+reheat. When the
tank temperature drops below the reheat temperature minus the reheat hysteresis
temperature, the tank heats up to the reheat temperature.
#
Code
[5.A]
[6-08]
Setpoint mode
#
Code
[5.B]
N/A
WD curve type
The weather dependent curve can be set using the 2-points method or the
Slope-Offset method. For more information about each method, see
4
curve" [
 144] and
"Slope-offset
only, and will correspond to the curve type set for the main zone. Changing the
curve type for the tank must be done in the main zone WD curve type [2.E]
menu. See
"Main
zone" [
#
Code
[5.E]
N/A
Maximum:
The maximum temperature that users can select
for the domestic hot water. You can use this
setting to limit the temperature at the hot water
taps.
The maximum temperature is NOT applicable
during disinfection function. See disinfection
function.
Heat pump ON hysteresis
2°C~40°C
Reheat hysteresis
2°C~20°C
Setpoint mode:
Fixed
Weather dependent
4
curve" [
 145]. The curve type in the menu is read
4
 154] for more information.
0: 2-points
1: Slope-Offset
11
Configuration
|
Description
Description
Description
Description
"2-points
Description
Installer reference guide
181