At times it is helpful to verify the operation of the fixture from the fixture itself. This process will help with troubleshooting other areas of the setup by val-
idating the MMS200 is working correctly.
To verify that MMS200 motion is working.
Navigate to the Test Tab
l
Navigate to Home, press and Hold Enter.
l
Note that the Mirror will start and complete the homing routine.
l
Upon completion, the motion system, motion position, and menu system are known to be working.
l
To verify that DMX values are being received by the MMS200
Ensure that there is a DMX source connected and sending data.
l
Navigate to the INFO Tab
l
Navigate to the DMX Tab,
l
Select a DMX channel to view the incoming data.
l
Upon completion the raw data through the link has been validated.
l
MMS200 User Guide --- (Details subject to change, and clarification)