Recommended actions
Event notification overflow
Alert
Event notification overflow
Cause
Event queue overflow resulting in event not being recorded.
Recommended actions
Acknowledge active events.
Capacity denied
Alert
Capacity denied
Cause
The device was unable to acquire the communication bandwidth required to
support the burst messaging specified.
Recommended actions
Bandwidth allocation pending
Alert
Bandwidth allocation pending
Quick Start Guide
1. Verify network ID and join key.
2. Verify network is in active network advertise.
3. Wait longer (30 minutes).
4. Check power module.
5. Verify the device is within range of at least one other device.
6. Power cycle device to try again.
1. Reduce the update rate on the transmitter.
2. Increase communication paths by adding more wireless points.
3. Check that the device has been online for at least an hour.
4. Check that the device is not routing through a "limited" routing
node.
5. Create a new network with an additional wireless gateway.
Quick Start Guide