Table 3-6: Failure alerts (continued)
Alert message
Instrument board
measurement failure
Instrument board
software error
Non-volatile memory
defect
Watchdog reset
executed
Radio failure
The Rosemount 4390 Wireless Transmitter supports up to 8 user
configurable alerts that can be set based on any supported device variables.
The following parameters are required for each user alerts:
Device variable to be monitored by the user alert
Alert name, used as a message to identify the alert
Users can choose to Enable or Disable the alert at any time
The Trigger point is the value that starts the alert
Deadband allows the user to add a tolerance range for the trigger value
The user must select if the alert is activated when the measurement is
either Below or Above the selected trigger point
Refer to
18
Figure
3-6.
Device status
Description
(Byte :: Bit)
0 :: 2
Due to an internal error, a
measurement was not performed
correctly.
6 :: 3
Unable to read the software version
on the Instrument Board
8 :: 1
The device has failed to access the
non-volatile memory.
8 :: 3
A watchdog reset has been
performed.
12 :: 4
The radio module has failed; the
device needs to be serviced or
replaced.
April 2021