Configuration Option
Description
UV Sensitivity
Factory set for low, medium, high, or very high sensitivity.
UV o i Fault Count
Number of consecutive o i failures required to produce an o i fault at the UV detector (field selectable from 1 to 30).
UV o i Frequency
Automatic o i test is performed on the UV sensor at intervals between one and ten minutes.
Arc Enabled
Box is checked if arc rejection is enabled for the UV detector.
Arc Rejection
Arc rejection for the UV detector can be set to low, medium, high, or very high.
IR Sensitivity
Factory set for low, medium, high, or very high sensitivity.
IR o i Fault Count
Number of consecutive o i failures required to produce an o i fault at the IR detector (field selectable from 1 to 30).
IR o i Frequency
Automatic o i test is performed on the IR sensor at intervals between one and ten minutes.
IR Config Mode
Indicates whether the IR detector is programmed to use TDSA or TDSA/Quick fire algorithm.
Auto o i Enabled
Box is checked if automatic o i is enabled.
Heater Disabled
Box is checked if the detector's optics heater is disabled (field is selectable).
Alarm Latching
Appropriate box is checked if the alarm fault and/or auxiliary relay is set for latching opening.
Fault Latching
Appropriate box is checked if the alarm fault and/or auxiliary relay is set for latching opening.
Aux. Latching
Appropriate box is checked if the alarm fault and/or auxiliary relay is set for latching opening.
Alarm Time Delay
This will delay sending the fire alarm message until the fire alarm has been generated uninterrupted for the specified time.
Aux. Relay Setting
The selected status condition will activate the auxiliary relay.
Normally De-Energized
Box is checked if the auxiliary relay is set for normally de-energized operation.
Aux. IR Alarm
Appropriate selection is made to indicate whether the auxiliary relay output uses TDSA and/or Quick fire algorithm.
3.1
Figure 7—X5200, X2200, X9800 Configuration tab
5
When Cancel and Save appear here
this indicates a change was made to the
detector's con guration. If the change is
not saved the detector will not retain the
new con guration.