Event Description
ASCII Mode
Calibration 4-20 mA
Configuration Changed
Delayed Fire
Detection Cycle Complete
Fire
*CLR: Fire
Fire A (High Speed)
Fire B (Unsustained)
Fire C (Sustained)
Fire D (Low level)
Fire E (Reduced o i Mode)
Hard Reset
Hard Reset Test Initiated
Hardware Manual o i Test
Hardware Manual o i Test Passed
Hardware Test Failure
Internal Hardware Test
Internal Memory Write
Logs Reset
MODBUS Action Error
MODBUS Address Error
MODBUS Timing Error
MODBUS Value Error
Normal
o i Calibration Passed
Power Down
Power Up
Pre-Alarm
*CLR: Pre-Fire
Relay 1
Relay 2
Reset Latched Outputs
Software Manual o i Test Passed
Software Manual o i Test with Active Output
Software Manual o i Test without Output
Software Reset Occurred
Sustained Fire Timer Initiated
Sustained Fire Timer Reset
*Events with 'CLR:' preceding the event name, indicate the event condition is no longer present. (Not all 'CLR:' events are listed in this document.)
3.1
X3301/X3302 EVENT LOG DESCRIPTIONS
Status Condition
Unit changed to ASCII communication protocol
A 4-20mA output calibration was initiated
Configuration changes were made.
Sustained Fire Mode. Sustained fire requirements have been met.
Persistent or Automotive fire cycle completed.
The requirements for at least one of the fire algorithms have been met.
Fire algorithm requirements are no longer met.
A Hi speed Regular fire was detected. (Automotive mode only)
A fire in duration of 3 seconds or less detected (flash fire). Event may also be present
during sustained fire events.
A fire in duration of 3 seconds or more detected.
Low Level Fire detected.
Fire detected while in Reduced Optical Integrity Mode.
System reset.
The internal watchdog test was requested
A Hardware Manual Optical Integrity (o i ) test was initiated. ( Mag o i or Test Line)
Hardware manual Optical Integrity test passed.
The external watchdog test failed to cause a system reset.
The external watchdog test was requested.
A write to flash memory has occurred.
All event logs have been erased. (Factory only)
MODBUS Communications error. The function code received in the query is not an
allowable action for the slave.
MODBUS Communications error. The data address received in the query is not an
allowable address for the slave.
MODBUS Communications timing error detected
MODBUS Communications error. A value contained in the query data field is not an
allowable value for the slave.
Normal operation.
Optical Integrity calibration passed.
Power was removed from the module.
Power was applied to the module.
Pre-fire alarm condition. No active output by default. Can be enabled by the user.
Requirements for Pre-Fire are no longer met.
Automotive mode. Relay 1 activated.
Automotive mode. Relay 2 activated.
Reset latched outputs. (Alarm and/or Fault conditions)
Software-initiated manual Optical Integrity test passed
Software-initiated manual Optical Integrity with active outputs started
Software-initiated manual Optical Integrity without active outputs started
Unit was reset via serial communication command
Sustained Fire Mode timer has been initiated.
Fire detected, but sustained alarm requirements not met