DESCRIPTION normal condition and notifies personnel of fire alarm or fault conditions. The X2200 UV Flame Detector meets the most stringent requirements worldwide with advanced detection The X2200 housing is available in copper-free aluminum capabilities and immunity to extraneous sources, or stainless steel, with NEMA/Type 4X and IP66/IP67 combined with a superior mechanical design.
High UV Sensitivity Three Red Flashes X2200. Therefore, an open circuit on the loop will Very High UV Sensitivity Four Red Flashes not cause the fault relay to change state or the Stand.
Artificial Lighting It is important to keep the detector viewing windows as The X2200 should not be located within 3 feet (0.9 m) free of contaminants as possible in order to maintain of artificial lights. Excess heating of the detector could maximum sensitivity.
IMPORTANT SAFETY NOTES Table 3—UV Absorbing Gases and Vapors The following is a partial list of compounds that exhibit WARNING significant UV absorption characteristics. These are also usually hazardous vapors. While generally of little Do not open the detector assembly in a hazardous consequence in small amounts, these gases can restrict area when power is applied.
Refer to Figure 2 and ensure that the plate will be The following factors should also be taken into oriented as shown when the X2200 is mounted and consideration: sighted. This will ensure proper operation of the system and will also minimize the accumulation of •...
Typically 16 AWG or 2.5 mm shielded cable is recommended. Wires should be stripped 3/8 inch (9 mm). A minimum input voltage of 18 Vdc must be present at the X2200. (10.2) 4X ø0.42 13.1 (1.1)
Page 10
Relay and 0-20 mA Output Models To ensure that the insulating material of the wiring Follow the instructions below to install the X2200. terminal block will not be affected by the heat generated by EOL resistors, observe the following guidelines when 1.
Page 11
X2200 DETECTOR FIRE ALARM PANEL mA – mA + SPARE SHIELD mA + REF mA – REF SPARE COM FIRE 2 COM AUX COM FIRE NO FIRE 2 NO AUX NO FIRE DEVICE 4 NC FIRE 2 NC AUX NC FIRE...
Page 12
–Vin –Vin –Vin –Vin O i TEST 1 O i TEST 1 Figure 10—X2200 Detector Wired for Non-Isolated 0 to 20 mA Current Figure 9—X2200 Detector Wired for Non-Isolated 0 to 20 mA Current Output (Sinking) Output (Sourcing) 24 VDC 24 VDC X2200 DETECTOR –...
Page 13
Addresses” section of this manual for switch setting procedure.) Figure 13—X2200 Terminal Block (EQP Model) SHIELD SHIELD COM 1 A COM 2 A COM 1 B COM 2 B PWR SHIELD PWR SHIELD +Vin +Vin –Vin –Vin C2089 Figure 14—Wiring Terminal Identification for X2200 EQP Model 15.1 95-8549...
Always observe precautions for NODE ADDRESS EQUALS THE ADDED VALUE OPEN = OFF handling electrostatic sensitive devices. OF ALL CLOSED ROCKER SWITCHES CLOSED = ON A2190 Figure 17—Address Switches for X2200 15.1 95-8549...
1 If fault continues, return device to factory for repair. To maintain maximum sensitivity and false alarm 2 See “Maintenance” section for cleaning procedure. resistance, the viewing windows of the X2200 must be kept relatively clean. Refer to the following procedure for cleaning instructions.
Refer to surface of the detector plate may eventually Table 1 in the X2200 Safety manual, number 95-8672, for deteriorate, resulting in reoccurring faults and frequency of proof tests. To test the system, perform the the need for plate replacement.
The auxiliary relay has normally open / normally closed contacts, normally energized or de-energized operation, and latching or non-latching operation. Associated Manuals List of X2200 related manuals: CURRENT OUTPUT (Optional)— 0 to 20 milliampere (±0.3 mA) dc current, with a TITLE...
Page 19
WIRING— 100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF Field wiring screw terminals are UL/CSA rated for up to INCIDENCE DECREASES. 14 AWG wire, and are DIN/VDE rated for 2.5 mm wire.
Prior to returning devices, contact the nearest local X2200 UV Flame Detector Detector Electronics office so that a Return Material Refer to the X2200 Model Matrix for details. Identification (RMI) number can be assigned. A Q9033 Mounting Arm is required: written statement describing the malfunction must –...
X2200 MODEL MATRIX MODEL DESCRIPTION X2200 UV Flame Detector X2200M UV Flame Detector with Molybdenum Tube TYPE MATERIAL Aluminum Stainless Steel (316) TYPE THREAD TYPE 4 Port, Metric M25 4 Port, 3/4" NPT TYPE OUTPUTS Relay Relay and 0-20 mA...
T6 (Tamb –40°C to +60°C) T5 (Tamb –40°C to +75°C) ZONE 21, AEx tb IIIC T80°C Tamb –40°C to +75°C IP66/IP67 The following accessories are FM approved for use with the X2200 Flame Detector: Part Number Description 102740-002 Magnet 007739-001...
Page 23
FM Approval and Performance Report – Continued RESPONSE CHARACTERISTICS Very High Sensitivity Distance Typical Response Time Fuel Size Mode feet (m) (seconds)* n-Heptane 1 x 1 foot 85 (25.9) Low Arc Methane 32 inch plume 100 (30.5) Low Arc *Add 2 seconds for EQP model. High Sensitivity Distance Typical Response Time...
Page 24
FM Approval and Performance Report – Continued FIELD OF VIEW Very High Sensitivity Typical Typical Distance Horizontal Vertical Fuel Size Response Time Response Mode feet (m) (degrees) (degrees) (seconds)* (seconds)* 42.5 n-Heptane 1 x 1 foot Low Arc (13) –45 –30 Methane 32 inch plume...
Page 25
FM Approval and Performance Report – Continued MODEL X2200M The X2200M uses a sensor that has a broader spectrum than the standard sensor. It is designed to detect fires with unusual chemistry such as black powder. Consult factory for usage recommendations. X2200M RESPONSE CHARACTERISTICS High Sensitivity Distance...
APPENDIX B CSA APPROVAL DIVISION CLASSIFICATION: Ultraviolet Flame Detector/Controller X2200 series, rated 18-30 Vdc, 2.5 Watts to 7.6 Watts. Relay contacts rated 5 Amps @ 30 Vdc. CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations Class I, Division 1, Groups B, C, and D (T5); Class II, Division 1, Groups E, F, and G (T5);...
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. • The Ultraviolet (UV) flame detector type X2200 is to be installed in places where there is a low risk of mechanical damage. •...
Page 28
IP66/IP67 for the apparatus. Unused conduit entries shall be closed with suitable blanking elements. NOTE For ATEX installations, the X2200 Flame Detector housing must be electrically connected to earth ground. The following accessories are ATEX approved for use with the X2200 Flame Detector: Part Number...
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. • The Ultraviolet (UV) flame detector type X2200 is to be installed in places where there is a low risk of mechanical damage. •...
The installation shall take into account, that the orientation arrow on the flame detector is directed upwards, as the view angle in this direction is <90°. The UV-flame detector corresponds to class 1. The following accessories are EN54-10 and EN54-17 approved for use with the X2200 Flame Detector: Part Number Description...