Factory Settings; Firmware Settings; Devices With Profibus Pa®, Foundation Fieldbus® And Hart® (All Sw Revisions) - ABB TTH300 Operating Instruction

Head-mount temperature transmitter
Hide thumbs Also See for TTH300:
Table of Contents

Advertisement

TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G

Factory settings

Firmware settings

The transmitter is configured ex works.
HART® devices from SW-Rev. 3.00
These devices can be reset to the factory setting, as well as to the setting according to the customer order.
With the menu item "Factory reset" in the service menu, the factory settings are reset to the factory settings according to the
following table (corresponds to standard configuration BS).
The menu item "Reset to Order" in the service menu is used to reset to the configuration ordered by the customer (default
configuration BS, customer-specific configuration without special user characteristic BF or customer-specific configuration with
special user characteristic BG).
The currently set HART protocol remains unchanged during a factory reset and a reset to order.
Devices with PROFIBUS PA®, FOUNDATION Fieldbus® and HART® (all SW revisions)
The following table with the corresponding parameter values applies.
Menu
Device Setup
Process Alarm
Display
Communication
1
Only applies to HART transmitters
2
Only applies to PROFIBUS PA transmitters
3
Only applies to FOUNDATION Fieldbus transmitters
4 The currently set HART protocol remains unchanged during any type of reset (all SW revisions).
Designation
Write protection
Input Sensor 1
Input Sensor 2
Input / output assignment
TAG
HART Descriptor
1
Display Value
Bargraph
1
Language
Contrast
HART Burstmode
1
2 3
Bus Address
Simulation mode
3
HART Protocol
Parameter
Sensor Type
R-Connection
Measured Range Begin
1
Measured Range End
1
Engeneering Unit
Damping
Fault signaling
1
Sensor Type
Measurement type
Status
1)
Factory setting
No
Pt100 (IEC60751)
Three-wire
0
100
Degrees °C
Off
To SW-Rev. 1.03: Overrange / high alarm 22 mA
From SW-Rev. 3:00: Underrange / low alarm
3.5 mA
1
Off
Sensor 1
To SW-Rev. 1.03: TIXXX-
1
Process Variable
Yes, output %
1
English
50 %
Off
1
2
3
126
/ 30
Off
3
HART 5 / 7
4
65
1