80
TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. I
... 10 Operation
Factory settings
Firmware settings
The transmitter is configured ex works.
HART® devices from SW-Rev.: 03.00
These devices can be reset to the factory setting as well as to the setting according to the customer order.
•
With the menu item "Factory reset" in the service menu, the settings are reset to the factory settings in accordance with the
following table (corresponds to default configuration BS).
•
The menu item "Reset to Order" in the service menu is used to reset the settings to the configuration ordered by the customer
(default configuration BS, customer-specific configuration without special user characteristic BF or customer-specific
configuration with special user characteristic BG).
The currently set HART protocol remains unchanged during "Factory reset" and "Reset to Order".
Devices with PROFIBUS PA®, FOUNDATION Fieldbus®, and HART® (all SW revisions)
The following table with the corresponding parameter values applies:
Menu
Designation
Device Setup
Write protection
Input Sensor 1
Process Alarm
Input Sensor 2
Input / output assignment
TAG
HART Descriptor
Display
Display Value
Bargraph
Language
Contrast
Communication
HART Burstmode
Bus Address
Simulation mode
HART Protocol
1) Only applies to HART transmitters
2
Only applies to PROFIBUS PA transmitters
3) Only applies to FOUNDATION Fieldbus transmitters
4) The currently set HART protocol remains unchanged during all types of reset (all SW revisions).
Parameter
–
Sensor Type
R-Connection
Measured Range Begin
Measured Range End
Engeneering Unit
Damping
Fault signaling
Sensor Type
Measurement type
–
1)
–
–
1)
–
–
–
1)
Status
2) 3)
–
3)
–
–
Factory setting
No
Pt100 (IEC60751)
Three-wire
1)
0
1)
100
Degrees °C
Off
1)
To SW-Rev.: 01.03:
Overrange / high alarm 22 mA
From SW-Rev.: 03.00:
Underrange / low alarm 3.5 mA
Off
Sensor 1
–
To SW-Rev.: 01.03: TIXXX-
Process Variable
Yes, output %
English
50 %
1)
Off
126
Off
HART 5 / 7