Factory Settings; Firmware Settings - ABB TTF300 Operating Instruction

Field-mount temperature transmitter
Hide thumbs Also See for TTF300:
Table of Contents

Advertisement

80
TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. I
... 10 Operation

Factory settings

Firmware settings

The transmitter is configured ex works.
HART® devices from SW-Rev.: 03.00
These devices can be reset to the factory setting as well as to the setting according to the customer order.
With the menu item "Factory reset" in the service menu, the settings are reset to the factory settings in accordance with the
following table (corresponds to default configuration BS).
The menu item "Reset to Order" in the service menu is used to reset the settings to the configuration ordered by the customer
(default configuration BS, customer-specific configuration without special user characteristic BF or customer-specific
configuration with special user characteristic BG).
The currently set HART protocol remains unchanged during "Factory reset" and "Reset to Order".
Devices with PROFIBUS PA®, FOUNDATION Fieldbus®, and HART® (all SW revisions)
The following table with the corresponding parameter values applies:
Menu
Designation
Device Setup
Write protection
Input Sensor 1
Process Alarm
Input Sensor 2
Input / output assignment
TAG
HART Descriptor
Display
Display Value
Bargraph
Language
Contrast
Communication
HART Burstmode
Bus Address
Simulation mode
HART Protocol
1) Only applies to HART transmitters
2
Only applies to PROFIBUS PA transmitters
3) Only applies to FOUNDATION Fieldbus transmitters
4) The currently set HART protocol remains unchanged during all types of reset (all SW revisions).
Parameter
Sensor Type
R-Connection
Measured Range Begin
Measured Range End
Engeneering Unit
Damping
Fault signaling
Sensor Type
Measurement type
1)
1)
1)
Status
2) 3)
3)
Factory setting
No
Pt100 (IEC60751)
Three-wire
1)
0
1)
100
Degrees °C
Off
1)
To SW-Rev.: 01.03:
Overrange / high alarm 22 mA
From SW-Rev.: 03.00:
Underrange / low alarm 3.5 mA
Off
Sensor 1
To SW-Rev.: 01.03: TIXXX-
Process Variable
Yes, output %
English
50 %
1)
Off
126
Off
HART 5 / 7
1)
1)
1)
1)
1)
2)
/ 30
3)
3)
4)