Menu: Calibrate; Menu: Diagnosis - ABB TTH300 Operating Instruction

Head-mount temperature transmitter
Hide thumbs Also See for TTH300:
Table of Contents

Advertisement

TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G

Menu: Calibrate

Menu / parameter
... / Calibrate
Measured range
Analog Out
... / Calibrate / Measured range
Apply Lower Range
Apply Upper Range
... / Calibrate / Analog Out
Trim 4 mA
Trim 20 mA

Menu: Diagnosis

Menu / parameter
... / Diagnosis
Looptest
Device status
SIL Check
Temp. of Electronics
Processvalue Sensor 1
Processvalue Sensor 2
Description
Select the 'Measured range' submenu.
Select the 'Analog Out' submenu.
The current reading (PV) is used as the lower range limit (4 mA).
The current reading (PV) is used as the upper range limit (20 mA).
Adjusts the current output with a 4 mA setpoint
Value range: 3.500 to 4.500 mA
Adjusts the current output with a 20 mA setpoint
Value range: 19.500 to 20.500 mA
Description
Simulates the current output signal
Value range: 3.500 to 23.600 mA
0.000 mA: ends looptest
Diagnostic notice (maintenance required, failure, etc.)
Select the 'SIL Check' submenu.
Not passed: Use tool for a detailed check of the current device configuration.
Passed: SIL Configuration Check successful. The device configuration is valid for SIL Safety applications.
Select the 'Temp. of Electronics' submenu.
Drag indicator: maximum or minimum device temperature
Select the 'Sensor 1 process data' submenu.
Drag indicator: maximum or minimum sensor temperature for sensor 1
Reset: Resets the values
Select the 'Sensor 2 process data' submenu.
Drag indicator: maximum or minimum sensor temperature for sensor 2
Reset: Resets the values