Input - Thermocouples / Voltages; Types; Voltages; Connection Lead - ABB TTH300 Operating Instruction

Head-mount temperature transmitter
Hide thumbs Also See for TTH300:
Table of Contents

Advertisement

TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G
Electrical data for inputs and outputs
Input - resistance thermometer / resistances
Resistance thermometer
Pt100 in accordance with IEC 60751, JIS C1604, MIL-T-24388
Ni in accordance with DIN 43760
Cu in accordance with recommendation OIML R 84
Resistance measurement
0 to 500 Ω
0 to 5000 Ω
Sensor connection type
Two-, three-, four-wire circuit

Connection lead

Maximum sensor line resistance
per line 50 Ω in accordance with NE 89
Three-wire circuit:
Symmetrical sensor line resistances
Two-wire circuit:
Compensation up to 100 Ω total lead resistance
Measurement current
< 300 μA
Sensor short circuit
< 5 Ω (for resistance thermometer)
Sensor wire break
Measuring range: 0 to 500 Ω > 0.6 to 10 kΩ
Measuring range: 0 to 5 Ω > 5.3 to 10 kΩ
Detection of sensor wire break in accordance with NE 89
in all lines

Sensor error signaling

Resistance thermometer:
Sensor short circuit and sensor wire break
Linear resistance measurement:
Sensor wire break

Input - thermocouples / voltages

Types

B, E, J, K, N, R, S, T in accordance with IEC 60584
U, L in accordance with DIN 43710
C in accordance with IEC 60584 / ASTM E988
D in accordance with ASTM E988

Voltages

−125 to 125 mV
−125 to 1100 mV
Connection lead
Maximum sensor line resistance:
per line 1.5 kΩ, total 3 kΩ
Detection of sensor wire break in accordance with NE 89
in all lines

Input resistance

> 10 MΩ

Internal reference junction Pt1000, IEC 60751 Cl. B

(no additional jumpers necessary)
Sensor error signaling
Thermocouple:
Sensor wire break
Linear voltage measurement:
Sensor wire break
Functionality input
Freestyle characteristic / 32-points-sampling point table
Resistance measurement up to a maximum of 5 kΩ
Voltages up to maximum 1.1 V
Sensor error adjustment
Through Callendar-Van Dusen coefficients
Through value table, 32 support points
Through single-point adjustment (offset adjustment)
Through two-point adjustment
Input functionality
1 Sensor
2 Sensors:
mean measurement,
differential measurement,
sensor redundancy,
Sensor drift monitoring
25

Advertisement

Table of Contents
loading

Table of Contents