4 Commissioning

4.4 Commissioning the unit

4.4.1 Factory settings

Three menu levels are available – Easy, User, and Advanced.
All settings found in the Easy Setup menu are also available
in the User setup. See Section 4.4.2, Commissioning using
the Easy Setup menu for Easy Setup instructions.
The LST100 is delivered with default factory settings as
shown in Table 4.1, Factory default settings.
Menu
Number
Setting
name
1
Operate Mode
Easy Setup
2
Length Unit
3
Empty Distance
4
Span
5
Blanking
6
Max Rate of Change
Calibration
1
Enable User Calibration
2
Measured Value of P1
3
Actual Value of P1
4
Measured Value of P2
5
Actual Value of P2
6
Enable Simulation
7
Simulated Voltage
8
Offset of 1000mV
9
Offset of 5000mV
Advanced
1
Measure Interval
Setup
2
Temp. Compensation
3
Temp. Unit
4
Temp. Offset
5
Min Power Level
6
Max Power Level
7
Invert Voltage
8
Failsafe
9
Factory Reset
10
User Password
Table 4.1: Factory default settings
14 OI/LST100-EN | LST100 – Ultrasonic level transmitter

4.4.2 Commissioning using the Easy Setup menu

The most common configuration parameters are summarized
in the Easy Setup menu. This menu provides the quickest way
to configure the device. Use the Easy Setup menu to select
dimensions, operating mode and engineering units.
For a detailed description of these menus and parameters,
see Section 5.2, Parameter descriptions .
1. Log on to the LST100 as described in Section 4.1 of this
Default value
Level
2. Select 1 from the Main Menu to display the Easy Setup menu:
feet
20.000 ft
19.150 ft
0.850 ft
1.500 ft
NO
0.003 ft
0.003 ft
0.003 ft
0.003 ft
NO
3. On the Easy Setup menu, select 1 to configure Operate
1 mV
1000 mV
5000 mV
2 s
YES
Fahrenheit
0.0 F
Level_1
Level_5
NO
LOW ALARM
NO
Level (1) – the LST100 measures
********
the distance from the bottom of the
tank to the surface of the liquid.
Empty
distance
manual. On the welcome screen are 5 menus: Easy, Calibration,
Monitor Console, Advanced Setup, and Diagnostics.
Mode . The options available are Level and Distance .
Select the desired mode by entering the associated
number. Click Enter.
IMPORTANT (NOTE)
After setting a value, select R to refresh the menu
with updated settings. Select B to return to the
previous menu without refreshing the menu with
updated settings.
Blanking
Span
Level
Distance (2) – the LST100 measures
the distance from the transmitter to
the surface of the liquid.
Blanking
Distance
Empty
distance
Span