Possible error messages – PROFIBUS PA® and FOUNDATION Fieldbus®
Range
Device status message
(on the display)
Sensor
Sensordrift
Sensor
S1 line resistance too high
Sensor
S1 short-circuit
Sensor
S1 wire break
Sensor
S2 line resistance too high
Sensor
S2 short-circuit
Sensor
S2 wire break
Operating conditions
S1 measuring range overflow
Operating conditions
S1 measuring range underflow
Operating conditions
S2 measuring range overflow
Operating conditions
S2 measuring range underflow
Operating conditions
Device temperature out of spec.
Electronics
Device error
Electronics
Device not calibrated
Electronics
Device being simulated
Electronics
Configuration error
Sensor
Sensor 1 + 2 redundancy failure
Sensor
Sensor 1 redundancy: short-circuit
Sensor
Sensor 1 redundancy: wire break
Sensor
Sensor 2 redundancy: short-circuit
Sensor
Sensor 2 redundancy, wire break
Note
If the remedial measures listed for the error message do not improve the status of the device, please consult ABB Service.
Cause
Outside of the specification
Maintenance required
Error
Error
Maintenance required
Error
Error
Outside of the specification
Outside of the specification
Outside of the specification
Outside of the specification
Outside of the specification
Error
Outside of the specification
Function check
Error
Error
Maintenance required
Maintenance required
Maintenance required
Maintenance required
Remedy
Sensor adjustment
Sensor 1: Remove corrosion at the connections or
reduce line length.
Sensor 1: Rectify short-circuit or replace sensor 1
Sensor 1: Rectify wire break or replace sensor 1
Sensor 2: Remove corrosion at the connections or
reduce line length.
Sensor 2: Rectify short-circuit or replace sensor 2
Sensor 2: Rectify wire break or replace sensor 2
Adapt S1 measuring range to suit measuring task
Adapt S1 measuring range to suit measuring task
Adapt S2 measuring range to suit measuring task
Adapt S2 measuring range to suit measuring task
Check environment; reposition measuring point if
required
Replace device
Calibrate device
Terminate simulation
Validate configuration
Check sensor / sensor connection
Rectify short-circuit at sensor 1 or replace sensor 1
Rectify break at sensor 1 or replace sensor 1
Rectify short-circuit at sensor 2 or replace sensor 2
Rectify break at sensor 2 or replace sensor 2
71