Operating Instruction
Head mounted Temperature Transmitter
OI/TTH300-EN
TTH300
coo

Advertisement

Table of Contents
loading

Summary of Contents for ABB TTH300

  • Page 1 Operating Instruction Head mounted Temperature Transmitter OI/TTH300-EN TTH300...
  • Page 2 Phone: +49 180 5 222 580 Fax: +49 621 381 931-29031 automation.service@de.abb.com © Copyright 2010 by ABB Automation Products GmbH Subject to changes without notice This document is protected by copyright. It assists the user in safe and efficient operation of the device.
  • Page 3: Table Of Contents

    1.5.1 Safety-/ warning symbols, note symbols....................8 1.5.2 TTH300-XXH - HART name plate......................9 1.5.3 TTH300-XXP - PROFIBUS PA name plate ..................10 1.5.4 TTH300-XXF - FOUNDATION Fieldbus name plate ................11 Transport safety information.........................11 Safety information for electrical installation....................12 Operating safety information ........................12 Returning devices............................12...
  • Page 4 HART output ............................64 10.2.2 PROFIBUS PA output ...........................64 10.2.3 FOUNDATION Fieldbus output......................64 10.3 Power supply (polarity safe) .........................64 10.3.1 HART power supply ..........................64 10.3.2 PROFIBUS / FOUNDATION Fieldbus power supply................64 Ex relevant specifications .........................65 11.1 TTH300-E1X, intrinsic safety ATEX ......................65 TTH300 OI/TTH300-EN...
  • Page 5 Contents 11.2 TTH300-H1X, intrinsic safety IECEx ......................65 11.3 Safety specifications for Intrinsic Safety ATEX / IECEx................65 11.4 TTH300-E2X, non-sparking ATEX .......................66 11.5 TTH300-L1X, intrinsically safe FM .......................66 11.6 TTH300-L2X, non-incendive FM ........................66 11.7 TTH300-R1X, intrinsically safe CSA ......................66 11.8 TTH300-R2X, non-incendive CSA .......................66 Type A and type AS LCD indicator......................67...
  • Page 6: Safety

    The device is designed for use exclusively within the stated values on the name plate and in the technical specifications (see section "Specifications"). • The maximum operating temperature must not be exceeded. • The permitted operating temperature must not be exceeded. • The housing degree of protection must be observed. TTH300 OI/TTH300-EN...
  • Page 7: Target Groups And Qualifications

    Prior to using corrosive and abrasive materials for measurement purposes, the operator must check the level of resistance of all parts coming into contact with the materials to be measured. ABB Automation Products GmbH will gladly support you in selecting the materials, but cannot accept any liability in doing so.
  • Page 8: Plates And Symbols

    Failure to observe this safety information may result in damage to or destruction of the product and/or other system components. IMPORTANT (NOTICE) This symbol indicates operator tips, particularly useful information, or important information about the product or its further uses. It does not indicate a dangerous or damaging situation. TTH300 OI/TTH300-EN...
  • Page 9: Tth300-Xxh - Hart Name Plate

    Safety 1.5.2 TTH300-XXH - HART name plate The name plate is located on the transmitter housing. TTH300 Automation Products GmbH Alzenau Germany 2008 O-Code: TTH300-E1H 2400045678 Ser.-No: 2065342 HW. Rev. 1.06 U = + 11...42 V, I = 4...20 mA, HART SW.
  • Page 10: Tth300-Xxp - Profibus Pa Name Plate

    Safety 1.5.3 TTH300-XXP - PROFIBUS PA name plate The name plate is located on the transmitter housing. TTH300 Automation Products GmbH Alzenau Germany 2009 O-Code: TTH300-E1P 2400034561 Ser.-No: 2064388 HW. Rev. 1.00 U = + 9...32 V, I = 12 mA, FISCO SW.
  • Page 11: Tth300-Xxf - Foundation Fieldbus Name Plate

    Safety 1.5.4 TTH300-XXF - FOUNDATION Fieldbus name plate The name plate is located on the transmitter housing. TTH300 Automation Products GmbH Alzenau Germany 2009 O-Code: TTH300-E1F 2400021437 Ser.-No: 2064567 HW. Rev. 1.00 U = + 9...32 V, I = 12 mA, FISCO SW.
  • Page 12: Safety Information For Electrical Installation

    According to EC guidelines for hazardous materials, the owner of hazardous waste is responsible for its disposal or must observe the following regulations for shipping purposes: All devices delivered to ABB Automation Products GmbH must be free from any hazardous materials (acids, alkalis, solvents, etc.).
  • Page 13: Disposal

    If it is not possible to dispose of old equipment properly, ABB Service can accept and dispose of returns for a fee. 1.10.2 RoHS Directive 2002/95/EC With the Electrical and Electronic Equipment Act (ElektroG) in Germany, the European Directives 2002/96/EC (WEEE) and 2002/95/EC (RoHS) are translated into national law.
  • Page 14: Use In Potentially Explosive Atmospheres

    Ex modem into the circuit outside the potentially explosive atmosphere. Ex relevant specifications See Chapter 11, "Ex relevant specifications" page 65. TTH300 OI/TTH300-EN...
  • Page 15: Design And Function

    3.1.1 Sensor redundancy To enhance system availability, the TTH300 has two sensor inputs. The second sensor input can be used redundantly for both resistance thermometers (2x three- wire circuit or 2x two-wire circuit) and thermocouples, or for a mixture of these. Sensor redundancy (or sensor backup) always involves measuring the temperature of the two sensors and calculating the mean value on the basis of this.
  • Page 16: Sensor Drift Monitoring

    The reading from channel 1 (Pt100) is mapped to the transmitter output as a process variable. Note Before configuring the maximum permissible sensor deviation for drift monitoring, sensor adjustment with respect to the sensor channel 1 value must be carried out with the help of the TTH300 DTM. TTH300 OI/TTH300-EN...
  • Page 17: Sensor Error Adjustment Using Callendar Van Dusen Coefficients

    1. Release the screw plug (3) for the cover of the connection head. 2. Open the cover (1). 3. Secure the transmitter (2) at the proper position on the cover, using the captive screws found in the transmitter. OI/TTH300-EN TTH300...
  • Page 18: Installation On The Measuring Inset

    6. Place the transmitter in the housing on the measuring inset and secure it. Important The toothed discs between measuring inset and transmitter are straightened when the screws are tightened. This enables them to grip the mounting screws. TTH300 OI/TTH300-EN...
  • Page 19: Installation On A Top Hat Rail

    Fig. 6 Installing / Removing the optional LCD display A00087 Fig. 7: Type AS LC display A00087 Fig. 8: Type A LC display Thanks to the LC display interface, the TTH300 can be operated using the LC display. OI/TTH300-EN TTH300...
  • Page 20: Electrical Connections

    “Technical specifications" section or the data sheet. Important The signal cable wires must be provided with wire end sleeves. The slotted screws of the connection terminals are tightened with a size 1 screwdriver (3.5 or 4 mm). TTH300 OI/TTH300-EN...
  • Page 21: Conductor Material

    Fig. 9 A LC display interface 5.2.1 Sensor connection Depending on the sensor model, a variety of conductor materials can be used for sensor connections. The integrated internal reference point makes it possible to directly connect thermal compensating lines. OI/TTH300-EN TTH300...
  • Page 22 1 x RTD, three-wire circuit and 1 x thermocouple 1) 2 x voltage measurement 1) 1 x thermocouple 1 x RTD, two-wire circuit and 1 x thermocouple 1) 1) Sensor backup/redundancy, sensor drift monitoring, mean measurement or differential temperature measurement TTH300 OI/TTH300-EN...
  • Page 23: Standard Application With 4

    ≥ 250 Ω (< 1,100 Ω). The signal line can be connected with or without grounding. When establishing a ground connection (minus side), make sure that only terminal side is connected to the equipotential bonding. OI/TTH300-EN TTH300...
  • Page 24: Standard Application With Profibus Pa And Foundation Fieldbus H1 Functionality

    When connecting these components, observe the following condition: ≤ U + 0.012 A x R Mmin Smin Where Minimum operating voltage of transmitter Mmin Minimum supply voltage of supply isolator / PCS input Smin Line resistance between transmitter and supply isolator TTH300 OI/TTH300-EN...
  • Page 25: Electrical Interconnection In Explosion Hazardous Areas

    Supply isolator / PCS input (intrinsically safe equipment) (related equipment) ≥ ≥ ≥ (cable) ≤ (cable) ≤ Field (Ex area) Control room (safe area) A00096 Fig. 15 A Transmitter B Supply isolator / PCS input with supply / Segment coupler OI/TTH300-EN TTH300...
  • Page 26: Installation In A Potentially Explosive Atmosphere

    When using the transmitter in Zone 0, you must ensure that impermissible electrostatic charging of the temperature transmitter is prevented (observe the warnings on the device). The user must ensure that the sensor instrumentation meets the requirements of applicable explosion protection standards. TTH300 OI/TTH300-EN...
  • Page 27: Atex - Zone 1 (0)

    The input for the supply isolator must have an [Ex ib] design. The user must ensure that the sensor instrumentation meets the requirements of applicable explosion protection standards. It can be installed in Zone 1 or Zone 0. OI/TTH300-EN TTH300...
  • Page 28: Atex - Zone 1 (20)

    For instruments in Zone 2, the transmitter must be installed in a suitable housing with ingress protection of at least IP 54. In the event of a disturbance, it must be ensured that the supply voltage cannot exceed the normal voltage by more than 40 %. TTH300 OI/TTH300-EN...
  • Page 29: Commissioning

    Configuration can be performed using the four control buttons on the front. Important Unlike configuration using the DTM or EDD, the functionality of the transmitter can only be changed to a limited extent if the LC display is used. OI/TTH300-EN TTH300...
  • Page 30: Configuration Via The Lc Display With Control Buttons

    Button functions Meaning Exit Exit menu Back Go back one submenu Cancel Cancel a parameter entry Next Select the next position for entering numerical and alphanumeric values Meaning Select Select submenu / parameter Edit Edit parameter Save parameter entered TTH300 OI/TTH300-EN...
  • Page 31: Process Display

    Call up information level. When Autoscroll mode is enabled, a symbol appears here and the operator pages are automatically displayed one after the other. Call up configuration level. The device is protected against changes to the parameter settings. OI/TTH300-EN TTH300...
  • Page 32: Switching To The Information Level (Profibus Pa And Foundation Fieldbus Only)

    Selects the operator page to be displayed Operator Page 2 Autoscroll When Multiplex mode is enabled, this initiates automatic switching of the operator pages on the process display. Signal View Selects the "Signal View" submenu, in which all dynamic readings are displayed TTH300 OI/TTH300-EN...
  • Page 33: Switching To The Configuration Level (Parameterization)

    Next 6. If necessary, select and set other decimal positions using the same procedure as described in steps 3 and 7. Use to confirm your setting. This concludes the procedure for changing a parameter value. OI/TTH300-EN TTH300...
  • Page 34 ABCDEFGHIJKLMNOPQ Next 6. If necessary, select and set other decimal positions using the same procedure as described in steps 3 and 4. 7. Use to confirm your setting. This concludes the procedure for changing a parameter value. TTH300 OI/TTH300-EN...
  • Page 35: Menu Structure For Hart Transmitters

    Calibrate Diagnostics Fig. 22 Process display The process display shows the current process values. Configuration level The configuration level contains all the parameters required for device commissioning and configuration. The device configuration can be changed on this level. OI/TTH300-EN TTH300...
  • Page 36: Parameter Overview

    HART Tag Address (Multidrop) HART Burstmode HART Resp. Preambles Calibrate Measured range Apply Lower Range Apply Upper Range Analog Output Trim 4 mA Trim 20 mA Diagnostics Looptest Device status Temp. of Electronics Processvalue Sensor 1 Processvalue Sensor 2 TTH300 OI/TTH300-EN...
  • Page 37: Hart Parameter Description

    Selects submenu "Measurement range" Damping 0 ... 100 s Configurable τ 63 % output signal damping value Factory Reset Yes / OK Resets configuration data, adjustment data trim high / low and DAC adjustment values to factory settings OI/TTH300-EN TTH300...
  • Page 38 Pt100 (JIS 1604) Pt100 resistance thermometer (JIS 1604) Pt200 resistance thermometer (JIS 1604) Pt200 (JIS 1604) Pt10 (IMIL 24388) Pt10 resistance thermometer (MIL 24388) Pt50 (IMIL 24388) Pt50 resistance thermometer (MIL 24388) Pt100 (MIL 24388) Pt100 resistance thermometer (MIL 24388) TTH300 OI/TTH300-EN...
  • Page 39 Sensor channel deactivated (sensor 2 only) R-Connection 2-wire Sensor connection type relevant for all Pt, Ni, Cu resistance thermometers 3-wire 4-wire 2-wire Resistance 0 ... 100 Ω Sensor line resistance relevant for all Pt, Ni, Cu resistance thermometers with a two-wire circuit OI/TTH300-EN TTH300...
  • Page 40 Value range Description ... / Device info Device Type Displays device type Serialnumber Displays serial number Softwareversion Displays software version Hardwareversion Displays hardware version HART Tag Displays HART tag HART Descriptor Displays HART descriptor Operation Time Displays operating hours TTH300 OI/TTH300-EN...
  • Page 41 Selects whether or not a bar graph is shown Bargraph View Output Current Output current of 4 ...20 mA signal Output % Output value as % of measurement range Language German Selects the menu language English Contrast 0 ... 100 % Sets the display contrast OI/TTH300-EN TTH300...
  • Page 42 ... / ... / Analog Output Trim 4 mA 3,500 ... 4,500 mA Adjusts the current output with a 4 mA setpoint Trim 20 mA 19,500 ... 20,500 mA Adjusts the current output with a 20 mA setpoint TTH300 OI/TTH300-EN...
  • Page 43: Activating Write Protection

    In write protection edit mode, an alphanumeric string of characters is displayed. 1. Enter master password "0110". 2. Use the "OK" button to confirm. "Write protection NO" is displayed. Note Master password "0110", for deactivating write protection, cannot be changed. OI/TTH300-EN TTH300...
  • Page 44: Diagnostic Information On The Lc Display

    Additionally, the diagnostic messages are divided into the following areas: Area Description Electronics Diagnostics for device hardware Sensor Diagnostics for sensor elements and supply lines Installation / Diagnostics for communication interface and parameterization / Configuration configuration Operating conditions Diagnostics for ambient and process conditions TTH300 OI/TTH300-EN...
  • Page 45: Description Of Diagnostic Information

    Below sensor range, sensor 1 Check measuring limits Installation / Single point calibration active, Terminate single-point Configuration sensor 1 adjustment Installation / Two point calibration active, Terminate two-point Configuration sensor 1 adjustment Sensor Measuring error, sensor 2 Check sensor connection OI/TTH300-EN TTH300...
  • Page 46 Operating conditions Limit HIGH Upper limit value: Warning Operating conditions Limit LOW Lower limit value: Warning Important If the remedial measures listed for the diagnostic information do not improve the status of the device, please consult ABB Service. TTH300 OI/TTH300-EN...
  • Page 47: Menu Structure For Profibus Pa And Foundation Fieldbus H1 Transmitters

    The information level contains the parameters and information that are relevant for the user. The device configuration cannot be changed on this level. Configuration level The configuration level contains all the parameters required for device commissioning and configuration. The device configuration can be changed on this level. OI/TTH300-EN TTH300...
  • Page 48: Overview Of Parameters On The Configuration Level

    MIN Value MAX Value Sensor 1 Sensor 2 Op. Time / Temp. Communication Display Language Contrast Operator Page 1 Line 1 Operator Page 2 Line 1 Line 2 Calibrate Reset Device Reset with Defaults 1) PROFIBUS PA only TTH300 OI/TTH300-EN...
  • Page 49: Profibus Pa And Foundation Fieldbus Parameter Description

    Pt100 (JIS 1604) Pt100 resistance thermometer (JIS 1604) Pt200 (JIS 1604) Pt200 resistance thermometer (JIS 1604) Pt10 (IMIL 24388) Pt10 resistance thermometer (MIL 24388) Pt50 (IMIL 24388) Pt50 resistance thermometer (MIL 24388) Pt100 (MIL 24388) Pt100 resistance thermometer (MIL 24388) OI/TTH300-EN TTH300...
  • Page 50 Callendar Van Dusen coefficient set 5 Sensor channel deactivated (sensor 2 only) Connection 1 / 2-wire Sensor connection type relevant for all Pt, Ni, Cu Connection 2 resistance thermometers 3-wire 4-wire 2-Wire Correction 1 / 0 ... 100 Ω 2-Wire Correction 2 TTH300 OI/TTH300-EN...
  • Page 51 ... / Device info Device ID Displays device ID Serial Number Displays serial number Software Version Displays software version Hardware Version Displays hardware version Device Tag Name Displays measuring point ID Descriptor Displays a user-defined text Operation Time Displays operating hours OI/TTH300-EN TTH300...
  • Page 52 40 to 60 °C Operating hours, 40 to 60 °C 60 to 85 °C Operating hours, 60 to 85 °C > 85 °C Operating hours, > 85 °C Communication excellent Displays the communication quality very good good none TTH300 OI/TTH300-EN...
  • Page 53 MIN Value Drag indicator: Minimum temperature, sensor 1 MAX Value Drag indicator: Maximum temperature, sensor 1 ... / ... / Sensor 2 MIN Value Drag indicator: Minimum temperature, sensor 2 MAX Value Drag indicator: Maximum temperature, sensor 2 OI/TTH300-EN TTH300...
  • Page 54 Selects the value displayed in line 2 Sensor 1 Sensor 2 Device Temperature AO Block 8.3.3.6 Menu: Calibrate Menu / Parameter Value range Description ... / Calibrate Reset Device Device restarts without configuration changes Reset with Defaults Device restarts with factory settings applied TTH300 OI/TTH300-EN...
  • Page 55: Diagnostic Information On The Lc Display

    Additionally, the diagnostic messages are divided into the following areas: Area Description Electronics Diagnostics for device hardware Sensor Diagnostics for sensor elements and supply lines Installation / Diagnostics for communication interface and parameterization / Configuration configuration Operating conditions Diagnostics for ambient and process conditions OI/TTH300-EN TTH300...
  • Page 56 The first line shows the area the diagnostics information -- F123.321-- comes from. Brief description The second line shows the error number. Information The next lines show a brief description of the error and Back Exit information on how to remedy it. TTH300 OI/TTH300-EN...
  • Page 57: Description Of Diagnostic Information

    Device temperature out of spec. Out of specification Check environment; reposition conditions measuring point if required Electronics Device error Error Replace device Electronics Device not calibrated Out of specification Calibrate device Electronics Device being simulated Functional check Terminate simulation OI/TTH300-EN TTH300...
  • Page 58 Sensor 2 redundancy, wire break Maintenance required Rectify break at sensor 2 or replace sensor 2 Important If the remedial measures listed for the diagnostic information do not improve the status of the device, please consult ABB Service. TTH300 OI/TTH300-EN...
  • Page 59: Acquisition Of Operating Values

    Values in the fields on the far left and right indicate operation of the transmitter outside the specified range. In this event, acknowledged properties of the transmitter might be limited, in particular, with respect to accuracy and service life. OI/TTH300-EN TTH300...
  • Page 60: Factory Settings

    Yes, output % Language English Contrast 50 % Communication HART Burstmode Status 2) 3) Bus address Simulation mode 1) Only applies to HART transmitters 2) Only applies to PROFIBUS PA transmitters 3) Only applies to FOUNDATION Fieldbus H1 transmitters TTH300 OI/TTH300-EN...
  • Page 61: Hardware Settings

    Switch 2 (S2) Simulation release Setting Function Simulation blocked Simulation enabled Important • Factory setting: Both switches "Off" (device not write-protected and simulation blocked) • With PROFIBUS PA devices, switch 2 must always be in the "Off" position. OI/TTH300-EN TTH300...
  • Page 62: Maintenance / Repair

    Faulty transmitters may not be placed into operation by the user. Repairs must be performed in the production plant. Cleaning When cleaning the exterior of meters, make sure that the cleaning agent used does not corrode the housing surface and the gaskets. TTH300 OI/TTH300-EN...
  • Page 63: Specifications

    Short circuit and wire break Via table of 32 sampling points Linear resistance measurement: Wire break Via single-point adjustment (offset adjustment) Via two-point adjustment Input functionality 1 sensor 2 sensors: mean measurement, differential measurement, sensor redundancy, sensor drift monitoring OI/TTH300-EN TTH300...
  • Page 64: Output

    – optional HMI display (transducer block 2) TTH300 discrete input 1 – extended diagnostics 1 (transducer block 3) TTH300 In ia hazardous area design discrete input 2 – extended diagnostics 2 (transducer block 3) HART communication resistor * Sensor1, sensor2, or difference, or mean Maximum power consumption 10.2.3 FOUNDATION Fieldbus output...
  • Page 65: Ex Relevant Specifications

    FISCO ENTITY Explosion protection ≤ 17.5 V ≤ 24.0 V Max. voltage = 30 V The TTH300 complies with the requirements of the Short circuit = 130 mA ≤ 183 mA 2) ≤ 250 mA ATEX Directive 94/9/EC current Approved for use in Zone 0, 1, and 2 Max.
  • Page 66: Tth300-E2X, Non-Sparking Atex

    Ex relevant specifications 11.4 TTH300-E2X, non-sparking ATEX Explosion protection The TTH300 complies with the requirements of ATEX Directive 94/9/EC Approved for use in Zone 2 Designation II 3 G Ex nA II T6 ABB manufacturer's declaration in accordance with ATEX Directive...
  • Page 67: Type A And Type As Lcd Indicator

    70 … 85 °C (158 … 185 °F) Humidity 0 … 100 %, condensation permitted Type A LCD Type AS LCD A00242 Fig. 26 Exit / Cancel Scroll forward Scroll back Select 1) Additional mechanical protection is required for this range OI/TTH300-EN TTH300...
  • Page 68: Safety Specifications For Intrinsic Safety Atex / Iecex

    85 °C U i / V = 9V, I i / I < 65.2 mA, P i = 101 mW C i < 0.4 µF, L i = 0 Control Drawing: SAP_214 750 Change from one to two columns TTH300 OI/TTH300-EN...
  • Page 69: Appendix

    Identification for intended use in potentially explosive atmospheres according Protection ATEX directive (marking in addition to CE marking) IEC standards FM Approvals (US) CSA International (Canada) Important All documentation, declarations of conformity, and certificates are available in ABB's download area. www.abb.com/temperature OI/TTH300-EN TTH300...
  • Page 70 Appendix TTH300 OI/TTH300-EN...
  • Page 71 Other toxic substances Radioactive Which substances have come into contact with the device? We hereby state that the devices/components shipped have been cleaned and are free from any dangerous or poisonous substances. Town/city, date Signature and company stamp OI/TTH300-EN TTH300...
  • Page 72: Index

    Ex relevant specifications ........67 Ex relevant specifications ......14, 25, 65 Note symbols .............8 Numerical entry............33 Factory settings............60 Features..............67 Operating safety information........12 Firmware settings.............60 Operation ..............30 Functionality.............63 Operator menu............32 Output signal............64 General information ..........62 Overview of parameters on the configuration level .48 TTH300 OI/TTH300-EN...
  • Page 73 Sensor connection type ...........63 Voltages ..............63 Sensor short circuit ..........63 Sensor wire break ............63 Warranty ..............7 Simulation mode ............64 Warranty provisions ...........7 Specifications..........6, 63, 67 WEEE Directive ............13 Standard application with HART functionality..23 Change from one to two columns OI/TTH300-EN TTH300...
  • Page 74 ABB has Sales & Customer Support expertise in over The Company’s policy is one of continuous product 100 countries worldwide. improvement and the right is reserved to modify the information contained herein without notice. www.abb.com/temperature Printed in the Fed. Rep. of Germany (02.2010) ©...