TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. G
Parameter description HART® (for HART®-devices from SW-Rev. 3.00)
Menu: Easy Setup
Menu / parameter
... / Easy Setup
Language
HART TAG
LONG TAG
Sensortype S1 (Sensortype S2)
Description
Selection of the menu language.
•
German
•
English
Measuring point tagging
•
8 characters
Long tag: Unique label of the device in the plant (HART 7)
•
32 characters
Selects sensor type:
•
0 to 500 Ω: Linear resistance measurement 0 to 500 Ω
•
0 to 5000 Ω: Linear resistance measurement 0 to 5000 Ω
•
Cal. Van Dusen 1: Callendar-Van Dusen coefficient set 1
•
Pt50 (IEC751): Resistance thermometer Pt50 (IEC751)
•
Pt100 (IEC751): Resistance thermometer Pt100 (IEC751)
•
Pt200 (IEC751): Resistance thermometer Pt200 (IEC751)
•
Pt500 (IEC751): Resistance thermometer Pt500 (IEC751)
•
Pt1000 (IEC751): Resistance thermometer Pt1000 (IEC751)
•
Pt50 (JIS1604): Resistance thermometer Pt50 (JIS1604)
•
Pt100 (JIS1604): Resistance thermometer Pt100 (JIS1604)
•
Pt50 (IMIL24388): Resistance thermometer Pt50 (MIL24388)
•
Pt100 (MIL24388): Resistance thermometer Pt100 (MIL24388)
•
Pt200 (MIL24388): Resistance thermometer Pt200 (MIL24388)
•
Pt1000 (MIL24388): Resistance thermometer Pt1000 (MIL24388)
•
Ni50 (DIN43760): Resistance thermometer Ni50 (DIN43716)
•
Ni100 (DIN43760): Resistance thermometer Ni100 (DIN43716)
•
Ni120 (DIN43760): Resistance thermometer Ni120 (DIN43716)
•
Ni1000 (DIN43760): Resistance thermometer Ni1000 (DIN43716)
•
Cu10 a=4260: Resistance thermometer Cu10 a=4260
•
Cu100 a=4260: Resistance thermometer Cu100 a=4260
•
Pt10 (IEC751): Resistance thermometer Pt10 (IEC751)
•
Pt10 (JIS1604): Resistance thermometer Pt10 (JIS1604)
•
Pt10 (IMIL24388): Resistance thermometer Pt10 (MIL24388)
51