TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. I

Electrical data for inputs and outputs

Input - resistance thermometer / resistances

Resistance thermometer
Pt100 in accordance with IEC 60751, JIS C1604, MIL-T-24388
Ni in accordance with DIN 43760
Cu in accordance with recommendation OIML R 84
Resistance measurement
0 to 500 Ω
0 to 5000 Ω
Sensor connection type
Two-, three-, four-wire circuit
Connection lead
Maximum sensor line resistance
per line 50 Ω in accordance with NE 89
Three-wire circuit:
Symmetrical sensor line resistances
Two-wire circuit:
Compensation up to 100 Ω total lead resistance
Measurement current
< 300 μA
Sensor short circuit
< 5 Ω (for resistance thermometer)
Sensor wire break
Measuring range: 0 to 500 Ω > 0.6 to 10 kΩ
Measuring range: 0 to 5 Ω > 5.3 to 10 kΩ
Detection of sensor wire break in accordance with NE 89 in
all lines
Sensor error signaling
Resistance thermometer:
Sensor short circuit and sensor wire break
Linear resistance measurement:
Sensor wire break

Input - thermocouples / voltages

Types
B, E, J, K, N, R, S, T in accordance with IEC 60584
U, L in accordance with DIN 43710
C in accordance with IEC 60584 / ASTM E988
D in accordance with ASTM E988
Voltages
−125 to 125 mV
−125 to 1100 mV
Connection lead
Maximum sensor line resistance:
per line 1.5 kΩ, total 3 kΩ
Detection of sensor wire break in accordance with NE 89 in
all lines
Input resistance
> 10 MΩ
Internal reference junction Pt1000, IEC 60751 Cl. B
(no additional jumpers necessary)
Sensor error signaling
Thermocouple:
Sensor wire break
Linear voltage measurement:
Sensor wire break

Functionality input

Freestyle characteristic / 32-points-sampling point table
Resistance measurement up to a maximum of 5 kΩ
Voltages up to maximum 1.1 V
Sensor error adjustment
Through Callendar-Van Dusen coefficients
Through value table, 32 support points
Through single-point adjustment (offset adjustment)
Through two-point adjustment
Input functionality
1 Sensor
2 Sensors:
mean measurement,
differential measurement,
sensor redundancy,
Sensor drift monitoring
37