Select from one of the methods below to rerange the transmitter. Each method is unique;
examine all options closely before deciding which method works best for your process.
Manually rerange the transmitter by entering range points
Entering range points with a field communicator
From the HOME screen, enter the Fast Key sequence
Device Dashboard Fast Keys
Entering range points with AMS Device Manager
1.
Right click on the device and select Configure.
2. Click Manual Setup and select Analog Output.
3. Enter upper and lower range values in the Range Limits box and click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
Entering range points with a local operator interface
Reference
Enter values using SCROLL and ENTER buttons.
Figure 2-6. Rerange with LOI
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
Rerange the transmitter with applied pressure source
Reranging using an applied pressure source is a way of reranging the transmitter without
entering specific 4 and 20 mA (1-5 Vdc) points.
Rerange with an applied pressure source using a field communicator
From the HOME screen, enter the Fast Key sequence
Device Dashboard Fast Keys
Configuration
Rerange by manually setting range points with a field communicator, AMS Device
Manager, or Local Operator Interface.
Rerange with a pressure input source and a field communicator, AMS Device Manager,
Local Operator Interface, or local zero and span buttons
Figure 2-6 on page 15
to rerange the transmitter using the Local Operator Interface.
RERANGE
ENTER VALUES
ENTER VALUES
APPLY VALUES
BACK TO MENU
EXIT MENU
2, 2, 2, 1
ENTER VALUES
LRV
URV
BACK TO MENU
EXIT MENU
2, 2, 2, 2