Emerson Rosemount 2088 Reference Manual page 57

Pressure transmitter with hart revision 5 and 7 selectable protocol
Hide thumbs Also See for Rosemount 2088:
Table of Contents

Advertisement

Section 4: Electrical Installation
March 2014
Transmitter case grounding
Always ground the transmitter case in accordance with national and local electrical codes. The
most effective transmitter case grounding method is a direct connection to earth ground with
minimal impedance. Methods for grounding the transmitter case include:
Figure 4-9. Internal ground connection
A. Internal ground location
B. External ground location
C. Positive
D. Negative
E. Test
Note
Grounding the transmitter case via threaded conduit connection may not provide sufficient
ground continuity.
48
Internal Ground Connection: The Internal Ground Connection screw is inside the FIELD
TERMINALS side of the electronics housing. This screw is identified by a ground symbol
(
). The ground connection screw is standard on all Rosemount 2088 transmitters.
Refer to
Figure 4-9 on page
External ground connection: The external ground connection is located on the exterior
of the transmitter housing. Refer to
with option T1.
C
D
E
48.
Figure on page
48. This connection is only available
A
B
Reference Manual
00809-0100-4108, Rev BA
Electrical installation

Advertisement

Table of Contents
loading

This manual is also suitable for:

G1s22a1b4e5q4p0021

Table of Contents