Section 5: Operation and Maintenance
March 2014
Performing 4-20mA/ 1-5 V output trim using local operator
interface
Figure 5-6. 4-20mA output trim using local operator interface
5.6.2
Performing digital-to-analog trim (4-20mA/ 1-5 V output
trim) using other scale
The Scaled 4-20 mA output Trim command matches the 4 and 20 mA points to a user selectable
reference scale other than 4 and 20 mA (for example, 2 to 10 volts if measuring across a 500 
load, or 0 to 100 percent if measuring from a Distributed Control System (DCS)). To perform a
scaled 4-20 mA output trim, connect an accurate reference meter to the transmitter and trim
the output signal to scale, as outlined in the Output Trim procedure.
Performing a 4-20/ 1-5 V mA output trim using other scale with
a field communicator
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field
Communicator to complete the 4-20 mA output trim using other scale.
Device dashboard Fast Keys
Performing a 4-20 mA/ 1-5 V output trim using other scale with
AMS Device Manager
1.
2.
3.
60
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
Right click on the device and under the Method drop down menu, move cursor over
Calibrate and select Analog Calibration.
Select Scaled Digital to Analog Trim.
Follow screen prompts to perform a 4-20mA/ 1-5 V output trim.
EXTENDED MENU
CALIBRAT
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
3, 4, 2, 2
Reference Manual
00809-0100-4108, Rev BA
CALIBRAT
ZERO TRIM
LOWER TRIM
UPPER TRIM
ANALOG TRIM
ANALOG TRIM
FACTORY RECALL
BACK TO MENU
EXIT MENU
Operation and maintenance