Emerson Rosemount 2090P Reference Manual
Emerson Rosemount 2090P Reference Manual

Emerson Rosemount 2090P Reference Manual

Pressure transmitters with 4-20 ma hart and 1-5 vdc low power protocol
Hide thumbs Also See for Rosemount 2090P:
Table of Contents

Advertisement

www.aotewell.com
Industry Automation
Reference Manual
00809-0100-4690, Rev FC
June 2011
Rosemount 2088, 2090P, and 2090F
Pressure Transmitters
with 4-20 mA HART and 1-5 Vdc Low Power Protocol
www.rosemount.com
sales@aotewell.com
+86-755-8660-6182

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Rosemount 2090P and is the answer not in the manual?

Questions and answers

Summary of Contents for Emerson Rosemount 2090P

  • Page 1 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC June 2011 Rosemount 2088, 2090P, and 2090F Pressure Transmitters with 4-20 mA HART and 1-5 Vdc Low Power Protocol www.rosemount.com sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 2 Aotewell Ltd www.aotewell.com Industry Automation sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 3: Rosemount 2088 And

    North American Response Center Equipment service needs. 1-800-654-7768 (24 hours—includes Canada) Outside of these areas, contact your local Emerson Process Management representative. The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
  • Page 4 Aotewell Ltd www.aotewell.com Industry Automation sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 5: Table Of Contents

    Rosemount 2088 ........2-5 Rosemount 2090P........2-5 Rosemount 2090F.
  • Page 6 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Overview ..........3-1 SECTION 3 Safety Messages .
  • Page 7 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 SECTION 4 Overview ..........4-1 Safety Messages .
  • Page 8 Ranges for Rosemount 2090F ......A-3 Ranges for Rosemount 2090P ......A-3 Load Limitations .
  • Page 9: Using This Manual

    SERVICE SUPPORT nearest Emerson Process Management representative. Within the United States, call the Emerson Process Management Instrument and Valves Response Center using the 1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will assist you with any needed information or materials.
  • Page 10: Models Covered

    OSHA, a copy of the required Material Safety Data Sheet (MSDS) for each hazardous substance identified must be included with the returned goods. Emerson Process Management Instrument and Valves Response Center representatives will explain the additional information and procedures necessary to return goods exposed to hazardous substances.
  • Page 11: Overview

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Section 2 Installation Overview ........page 2-1 Safety Messages .
  • Page 12 Management for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous. • Use only bolts supplied or sold by Emerson Process Management as spare parts. • Refer to page A-7 for a complete list of spare parts.
  • Page 13: General Considerations

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Measurement accuracy depends on proper installation of the transmitter and GENERAL impulse piping. Mount the transmitter close to the process and use a CONSIDERATIONS minimum of impulse piping to achieve the best accuracy.
  • Page 14: Hart Installation Flowchart

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 HART INSTALLATION FLOWCHART Figure 2-1. HART Installation Flowchart START HERE Bench Calibration? Field Install Configure Security and Alarm Configure Verify (page 2-15) Mount Transmitter Set Units Review (page 2-5)
  • Page 15: Installation Procedures

    Rosemount 2090P The Rosemount 2090P is designed to be mounted directly to the process pipe using a weld spud (see Figure 2-7). Mount the transmitter using an existing weld spud or install a new one using the instructions on page 2-11.
  • Page 16: Rosemount 2088

    ) also available as options. † DIN 16288 G Male, RC Female (PT ), and M20 1.5 Male also available. Certification Tag Rosemount 2090P (1 -in.) Flush Mount 3.9 (100) 5.1 (130) 4.3 (110) Optional Display Cover Terminal (120) Connections Transmitter Circuitry 5.1(130)
  • Page 17: Rosemount 2090P

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Rosemount 2090P (1-in. Flush Mount) External Zero/Span (under Nameplate) 5.1 (130) Nameplate 4.3 (110) (100) Optional Display Cover Terminal Connections Transmitter Circuitry Side 4.7 (140) 5.75 (146)
  • Page 18 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Figure 2-3. Transmitter Mounting Configurations with Optional Bracket. PIPE MOUNTING PANEL MOUNTING 5.0 (125) 3.9 (100) 4.3 (110) (100) (139) (90) (160) 1.25 (32) (70) 6.0 (150) (63)
  • Page 19: Mounting Requirements

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 The piping between the process and the transmitter must accurately transfer Impulse Piping the pressure to obtain accurate measurements. There are six possible sources of impulse piping error: pressure transfer, leaks, friction loss (particularly if purging is used), trapped gas in a liquid line, liquid in a gas line, and density variations between the legs.
  • Page 20 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Steam Flow Measurement • Place taps to the side of the line. • Mount the transmitter below the taps to ensure that impulse piping will remain filled with condensate.
  • Page 21: Rosemount 2090P

    June 2011 Process Connections Rosemount 2090P Installing the Rosemount 2090P transmitter involves attaching a weld spud to the tapped process vessel, attaching the transmitter to the weld spud, and making electrical connections. If you intend to use an existing weld spud, proceed to the transmitter section of this installation procedure (page 2-12).
  • Page 22: Transmitter

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Transmitter After the weld spud has cooled, remove the heat sink and install the PTFE gasket into the weld spud. Ensure that the gasket is properly positioned within the weld spud;...
  • Page 23 2.37 (60) Code “C” in Model Structure or P/N 02088-0195-0005 Process Vessel Figure 2-6. PTFE Gasket Placement. PTFE Gasket Figure 2-7. Rosemount 2090P Mounting Configuration Using a Weld Spud. Nameplate DETAIL OF WELD SPUD Weld Spud 100–125 Amps Bevelled Edge recommended ¼–20...
  • Page 24: Rosemount 2090F

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Rosemount 2090F The Rosemount 2090F hygienic pressure transmitter is designed to be installed directly to a sanitary fitting. The transmitter is available with either a - or 2-in.
  • Page 25: Configure Security And Alarm

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Do not apply torque directly to the electronics housing. Rotation between the electronics housing and the process connection can damage the electronics. To avoid damage, apply torque only to the hex-shaped process connection.
  • Page 26: Configuring Transmitter Security And Alarm Jumper

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 NOTE If either the alarm or security jumper is dislodged or removed from its position, the transmitter reverts to default alarm or security settings of: Alarm: Output high;...
  • Page 27: Without A Display Installed

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Figure 2-9. Transmitter Alarm and Security Jumper Locations Without LCD Display Low Power without LCD Display Alarm Alarm Security Security With LCD Display Low Power with LCD Display Security Alarm Alarm...
  • Page 28: Electrical Considerations

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 The wiring terminations on the Rosemount 2088/2090 are located in the side ELECTRICAL of the transmitter housing marked “FIELD TERMINALS.” Access to these CONSIDERATIONS terminations is required during installation and may be necessary during periodic calibration of the transmitter.
  • Page 29 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Wiring Do not connect the power signal wiring to the test terminals. Voltage may burn out the reverse-polarity protection diode in the test connection. NOTE Use shielded twisted pairs to yield best results.
  • Page 30 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Figure 2-11. Rosemount 2088/2090 Transmitter Signal Wiring Terminals Positive Negative Test Figure 2-12. 4-20 mA HART Transmitter Wiring Diagram Power Supply 250 Figure 2-13. 1-5 mA Vdc HART Low Power Transmitter Wiring Power Supply Voltmeter...
  • Page 31: Signal Wiring

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 The transmitter will withstand electrical transients of the energy level usually Transient Protection encountered in static discharges or induced switching transients. However, Terminal Block high-energy transients, such as those induced in wiring from nearby lightning strikes, can damage the transmitter.
  • Page 32 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 2-22 sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 33: Overview

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Section 3 Configuration Overview ........page 3-1 Safety Messages .
  • Page 34: Commissioning

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Commissioning consists of testing the transmitter and verifying transmitter COMMISSIONING configuration data. The Rosemount 2088/2090 can be commissioned either before or after installation. Commissioning the transmitter on the bench before installation using a Field Communicator or AMS Device Manager ensures that all transmitter components are in working order.
  • Page 35 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Figure 3-1. 4-20 mA HART Transmitter Wiring Diagram Power Supply 250 Figure 3-2. 1-5 Vdc HART Low Power Transmitter Wiring Power Supply Voltmeter sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 36: Configuration Data Review

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 CONFIGURATION DATA NOTE Information and procedures in this section that make use of Field REVIEW Communicator fast key sequences and AMS Device Manager assume that the transmitter and communication equipment are connected, powered, and operating correctly.
  • Page 37: Field Communicator Menu Tree

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 FIELD COMMUNICATOR MENU TREE Figure 3-3. Rosemount 2088/2090 HART menu tree for 4-20 mA HART PROCESS Pressure VARIABLES Percent Range 1 Self test Analog Output 2 Status 1 Keypad Input 1 TEST DEVICE...
  • Page 38 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Figure 3-4. Rosemount 2088 HART Menu Tree for 1-5 Vdc Low Power 1 PROCESS 1 Pressure 1 Self Test VARIABLE 2 Percent Range 2 Status 1 Keypad Input 1 DEVICE 3 Analog Output...
  • Page 39: Fast Key Sequence

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 FAST KEY SEQUENCE Table 3-1. HART Fast Key Sequences for the Rosemount 2088/2090. A check () indicates the basic configuration parameters. At minimum, these parameters should be verified as part of the configuration and startup procedure Function HART Fast Key Sequence...
  • Page 40: Check Output

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Before performing other transmitter on-line operations, review the digital CHECK OUTPUT output parameters to ensure that the transmitter is operating properly and is configured to the appropriate process variables. Process Variables The process variables for the Rosemount 2088/2090 provide the transmitter output, and are continuously updated.
  • Page 41: Method 1: Rerange With A Field Communicator Or Ams Device Manager

    NOTE Transmitters are shipped from Emerson Process Management fully calibrated per request or by the factory default of full scale (zero to upper range limit). NOTE Regardless of the range points, the Rosemount 2088/2090 will measure and report all readings within the digital limits of the sensor.
  • Page 42: And A Pressure Source Or Process Pressure

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Method 3: Rerange Using the Local Zero and Span Buttons and a Pressure Source or Process Pressure The Rosemount 2088/2090 is equipped with local zero and span adjustment buttons.
  • Page 43: Field Communicator

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 The Damping command changes the response time of the transmitter to Damping smooth variations in output readings caused by rapid changes in input. Determine the appropriate damping setting based on the necessary response time, signal stability, and other requirements of the loop dynamics of your system.
  • Page 44: Field Communicator

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 The factory default is Percent of Range (M5 option) or Engineering Units (M7 LCD Display option). The LCD Display Configuration command allows customization of the Configuration for 4-20 LCD display to suit application requirements.
  • Page 45 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 To specify decimal point position: a. Select 1 Sel dec pt pos. Choose the decimal point representation that will provide the most accurate output for your application. For example, when outputting between 0 and 75 GPM, choose XX.XXX or use the decimal point examples below: XXXXX...
  • Page 46: Detailed Setup

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 DETAILED SETUP As part of normal operation, the Rosemount 2088/2090 Pressure Transmitter Failure Mode Alarm and continuously monitors its own operation. This automatic diagnostic routine is Saturation a timed series of checks repeated continuously.
  • Page 47: Field Communicator

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Burst Mode sets the transmitter to maintain digital contact with a Digital Burst Mode Control System that has custom software to support burst mode. When the Rosemount 2088 transmitter is configured for burst mode, it provides faster digital communication from the transmitter to the control system by eliminating the time required for the control system to request information from the...
  • Page 48: Field Communicator

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 If the transmitter electronics board, sensor module, or LCD display is repaired Alarm Level Verification or replaced, verify the transmitter alarm level before returning the transmitter to service.
  • Page 49: Multidrop Communication

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Multidropping transmitters refers to the connection of several transmitters to a MULTIDROP single communications transmission line. Communication between the host COMMUNICATION and the transmitters takes place digitally with the analog output of the transmitters deactivated.
  • Page 50 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 To change the address of a multidropped transmitter, follow these fast key Changing a Transmitter sequences. To activate multidrop communication, the transmitter address Address must be changed to a number from 1 to 15.
  • Page 51: Overview

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Section 4 Operation and Maintenance Overview ........page 4-1 Safety Messages .
  • Page 52: Calibration Overview

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Calibration is defined as the process required to optimize transmitter accuracy CALIBRATION over a specific range by adjusting the factory sensor characterization curve OVERVIEW located in the microprocessor.
  • Page 53 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Figure 4-1. Transmitter Data Flow with Calibration Options Transmitter Ranged 0 to 100 inH Transmitter Electronics Module Microprocessor Sensor Digital PV Signal Sensor Input Pressure 20.00 mA Input Device...
  • Page 54: Sample Calculation For A Standard 2088

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Sample Calculation For A Standard 2088 Step 1: Determine the performance required for your application. Required Performance: 0.50% of span Step 2: Determine the operating conditions. Transmitter: 2088G, Range 1 [URL=30 psi (2,1 bar)] Calibrated Span:...
  • Page 55: Analog Output Trim

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 The Analog Output Trim commands allow you to adjust the transmitter’s ANALOG OUTPUT TRIM current output at the 4 and 20 mA (1 and 5 Vdc) points to match the plant standards.
  • Page 56: Ams

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Right click on the device and select “Calibrate,” then “D/A Trim” from the menu 1. Click Next after setting the control loop to manual. 2.
  • Page 57: Field Communicator

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Field Communicator 4-20 mA Fast Keys 1, 2, 3, 2, 2 Right click on the device and select “Calibrate,” then “Scaled D/A trim” from the menu 1.
  • Page 58: Sensor Trim

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 SENSOR TRIM Trim the sensor using either sensor or zero trim functions. Trim functions vary Sensor Trim Overview in complexity and are application-dependent. Both trim functions alter the transmitter’s interpretation of the input signal.
  • Page 59: Field Communicator

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Zero Trim NOTE The transmitter must be within three percent of true zero (zero-based) in order to calibrate with zero trim function. Field Communicator 4-20 mA Fast Keys 1, 2, 3, 3, 1 Calibrate the sensor with a Field Communicator using the zero trim function...
  • Page 60: Ams

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 NOTE Select pressure input values so that lower and upper values are equal to or outside the 4 and 20 mA (1 and 5 Vdc) points. Do not attempt to obtain reverse output by reversing the high and low points.
  • Page 61: Overview

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Section 5 Troubleshooting Overview ........page 5-1 Safety Messages .
  • Page 62 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Table 5-1. Rosemount 2088/2090Troubleshooting for 4-20 mA output. Symptom Corrective Actions Transmitter milliamp reading is zero Verify power is applied to signal terminals Check power wires for reversed polarity Verify terminal voltage is 10.5 to 42.4 Vdc Check for open diode across test terminal Transmitter Not Communicating with...
  • Page 63: Diagnostic Messages

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 In addition to the output, the LCD displays abbreviated operation, error, and DIAGNOSTIC warning messages for troubleshooting the transmitter. Messages appear MESSAGES according to their priority, with normal operating messages appearing last. To determine the cause of a message, use a Field Communicator to further interrogate the transmitter.
  • Page 64: Press Limit

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 PRESS LIMIT The process variable read by the transmitter is outside of sensor range limits. CURR FIXED The transmitter is in multidrop mode. The analog output is not tracking pressure changes.
  • Page 65: Write Protect

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 WRITE PROTECT The write protect (SECURITY) jumper is set to disable changes to the transmitter configuration data. Refer to “Transient Protection Terminal Block” on page 2-21 for more information on the security jumper. Field Communicator Diagnostics Table 5-2 is a list of messages used by the Field Communicator (HC) and their corresponding descriptions.
  • Page 66 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Message Description Device is in write-protect mode. Press YES to turn the Device write protected. Do you Field communicator off and lose the unsent data. still want to shut off? Asks whether the value of the variable should be...
  • Page 67 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Message Description There is no more memory available to store additional Out of memory for hotkey hotkey items. Unnecessary items should be deleted to configuration.
  • Page 68: Disassembly Procedures

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Do not remove the instrument cover in explosive atmospheres when the DISASSEMBLY circuit is live. PROCEDURES Follow these steps: Remove from Service • Follow all plant safety rules and procedures. •...
  • Page 69: Reassembly Procedures

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 REASSEMBLY PROCEDURES 1. Remove the cable connector from its position inside of the internal black Attach the Electronics cap and attach it to the electronics board. Board 2.
  • Page 70 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 5-10 sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 71: Performance Specifications

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Appendix A Reference Data Performance Specifications ..... . . page A-1 Functional Specifications .
  • Page 72: Vibration Effect

    SWC 2.5 kV Crest,1 MHz waveform General Specifications Tested to IEC 801-3. FUNCTIONAL Service SPECIFICATIONS Rosemount 2088 Liquid, gas, and vapor applications. Rosemount 2090P Liquid, gas, vapor, and high-viscosity applications. Rosemount 2090F Liquid, gas, vapor, and hygienic applications. Rangedown 20 to 1 sales@aotewell.com +86-755-8660-6182...
  • Page 73: Ranges For Rosemount 2088

    1.5 psi (103 mbar) 30 psi (2,1 bar) 7.5 psi (517 mbar) 150 psi (10,3 bar) 40 psi (2,76 bar) 300 psi (20,7 bar) Ranges for Rosemount 2090P Range Minimum Span URL/Max.span/Sensor Limit 1.5 psi (103 mbar) 30 psi (2,1 bar) 7.5 psi (517 mbar)
  • Page 74: Zero Elevation And Suppression

    Rosemount 2088 Silicone fill sensor: –40 to 250 °F (–40 to 121 °C). Inert fill sensor: –22 to 250 °F (–30 to 121 °C). Rosemount 2090P –4 to 250 °F (–20 to 121 °C). Rosemount 2090F –4 to 284 °F (–20 to 140 °C).
  • Page 75: Humidity Limits

    Rosemount 2088 –50 to 230 °F (–46 to 110 °C). –40 to 185 °F (–40 to 85 °C) with LCD display. Rosemount 2090P –50 to 185 °F (–45 to 85 °C). Rosemount 2090F –22 to 185 °F (–30 to 85 °C).
  • Page 76: Non-Wetted Parts

    00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 316L stainless steel or Alloy C-276. Rosemount 2088 316L stainless steel. Rosemount 2090P 316L stainless steel. Rosemount 2090F Process Connector 316L stainless steel or Alloy C-276. Rosemount 2088 316L stainless steel.
  • Page 77: Spare Parts

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 SPARE PARTS Figure A-1. Replacement Parts for the Rosemount 2088. LCD Display Cover Assembly includes LCD Cover and O-ring Item No. Part Description Part Number Spares Category Transmitters (Output Code S) 1, 2...
  • Page 78 Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Figure A-2. Replacement Parts for the Rosemount 2090P. LCD Display Cover Assembly includes LCD Cover and O-ring Item No. Part Description Part Number Transmitters (Output Code S)
  • Page 79 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Figure A-3. Replacement Parts for the Rosemount 2090F. LCD Display Cover Assembly includes LCD Cover and O-ring Item No. Part Description Part Number Transmitters (Output Code S) Electronics Cover (with O-ring) 03031-0292-0001 LCD Display Cover Assembly...
  • Page 80: Ordering Information

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 ORDERING INFORMATION Table A-1. Rosemount 2088 Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
  • Page 81 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Table A-1. Rosemount 2088 Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
  • Page 82 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Table A-1. Rosemount 2088 Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
  • Page 83 Rosemount 2088 and 2090 June 2011 Table A-2. Rosemount 2090P Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
  • Page 84 Rosemount 2088 and 2090 June 2011 Table A-2. Rosemount 2090P Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
  • Page 85 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Table A-3. Rosemount 2090F Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
  • Page 86 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Table A-3. Rosemount 2090F Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
  • Page 87: Overview

    Rosemount Inc. — Chanhassen, Minnesota USA Approved Manufacturing Locations Emerson Process Management GmbH & Co. — Wessling, Germany Emerson Process Management Asia Pacific Private Limited — Singapore Beijing Rosemount Far East Instrument Co., LTD — Beijing, China The EC declaration of conformity for all applicable European directives for this European Directive product can be found on the Rosemount website at www.rosemount.com.
  • Page 88: European Certifications

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 C6 Explosion-proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof for Class II, Division 1, Groups E, F, G, Class III, indoor and outdoor hazardous locations.
  • Page 89: Japanese Certifications

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Special Conditions for Safe Use (x): The user must ensure that the maximum rated voltage and current (36 volts, 24 mA, D.C.) are not exceeded. All connections to other apparatus or associated apparatus shall have control over this voltage and current equivalent to a category “ib”...
  • Page 90: Australian Certifications

    Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Certificate Description TC15874 2088 with Alloy C-276 wetted parts (with display) TC15873 2088 with Alloy C-276 wetted parts (no display) TC15872 2088 with SST wetted parts (with display) TC15871 2088 with SST wetted parts (no display) Australian Certifications...
  • Page 91 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Special Conditions for Safe Use (X): The device contains a thin wall diaphragm. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected.
  • Page 92 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Special Conditions for Safe Use Symbol “X” is used to denote specific conditions of use: • This apparatus is not capable of withstanding the 500 V r.m.s. insulation test required by Clause 6.4.12 of GB3836.4-2000.
  • Page 93 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 E3 China (NEPSI) Flameproof NEPSI Certificate No. (2088 manufactured in Chanhassen, MN): GYJ111062 NEPSI Certificate No. (2088 manufactured in Beijing, China): GYJ071128 NEPSI Certificate No. (2090 manufactured in Beijing, China): GYJ071130 2090 RTC &...
  • Page 94 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 N3 China Type n Non - Sparking NEPSI Cert No. (2088 manufactured in Beijing, China): GYJ101126X Ex nA nL IIC T5 Special Conditions for Safe Use (x) Symbol “X”...
  • Page 95 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Figure B-1. F.M. Intrinsically Safe Approvals for Rosemount 2088 and 2090 sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 96 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 B-10 sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 97 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 B-11 sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 98 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 B-12 sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 99 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 B-13 sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 100 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 B-14 sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 101 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Figure B-2. CSA Intrinsic Safety Approvals for Rosemount 2088 and 2090 B-15 sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 102 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 B-16 sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 103 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 B-17 sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 104 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 B-18 sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 105 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Appendix C Glossary Some of the terms used in this manual relate specifically to the operation of Rosemount transmitters, hand-held Field Communicators, and other Rosemount products.
  • Page 106 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual 00809-0100-4690, Rev FC Rosemount 2088 and 2090 June 2011 Lowest value of the measured variable that the analog output of the Lower Range Value transmitter is currently configured to measure. (LRV) The connection of several transmitters to a single communications Multidropping transmission line.
  • Page 107 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual Rosemount 2088 and 2090 00809-0100-4690, Rev FC June 2011 Index Dimensional drawings ..2-10 Model 2088 ....3-18 .
  • Page 108 Aotewell Ltd www.aotewell.com Industry Automation Reference Manual Rosemount 2088 and 2090 00809-0100-4690, Rev FC June 2011 ...4-1 Sensor Troubleshooting Module ....3-8 .
  • Page 109 Aotewell Ltd www.aotewell.com Industry Automation sales@aotewell.com +86-755-8660-6182 HongKong|UK|China...
  • Page 110 June 2011 Standard Terms and Conditions of Sale can be found at www.rosemount.com\terms_of_sale The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. SuperModule and Coplanar trademarks of Rosemount Inc.