- after exchanging the unit, the measuring range recorded in the
instrument is applied as standard.
The transmitter even retains its scaling with the voltage
disconnected.
Measuring range, see table (below).
3
The maximum settings for the manual scaling
- the values are not expressly given in the table. The maximum limits
can be calculated as follows:
X = difference between MIN. and MAX. value of the standard scaling
(Max. value of standard) + (50 % of X)
(Min. value of standard) - (50 % of X)
- It is thus possible to scale beyond the measuring range, e.g. for the
adjustment of the scaling limits to standard values of a PLC.
However, the physical measurement range limits are the deciding
factor when defining alarms.
Parameter
Temperature
relative humidity
WMO relative humidity
Unit
probe
°C
6611
°F
6611
°C
6612
°F
6612
°C
6613
°F
6613
°C
6614, 6617
°F
6614, 6617
°C
6615
°F
6615
% RH
% RH,
testo 6681
- 1.2 Product description 13
Measuring
range
Physical
at 1013 hPa
MIN
MAX
-20
-4
+158
-30
+150
-22
+302
-70
+180
-94
+356
-40
+180
-40
+356
-40
+120
-40
+248
0
+100
0
+100
Standard
scaling
MUF
measuring
range
MIN MAX
+70
-20
+70
-4
+158
-30
+150
-22
+302
-40
+180
-40
+356
-40
+180
-40
+356
-40
+120
-40
+248
0
+100
0
+100