6 PROFIBUS-DP Option Drive Parameters

6
PROFIBUS-DP Option Drive Parameters
Confirm proper setting of the all parameters in
communications.
No.
b1-01
Frequency Reference Selection
b1-02
Run Command Selection
Operation Selection after
F6-01
Communications Error
External Fault Detection
F6-02
Conditions (EF0)
Stopping Method for External
F6-03
Fault from Communication
Option Board
F6-04
bUS Error Detection Delay Time
F6-30
Node Address
F6-31
Clear Mode Selection
F6-32
PROFIBUS Map Selection
* 1. To start and stop the drive with the PROFIBUS-DP master device using serial communications, set
b1-02 to "3". To control the frequency reference of the drive via the master device, set b1-01 to "3".
* 2. If F6-03 is set to 3, then the drive will continue to operate when an EF0 fault is detected. Take proper
safety measures, such as installing an emergency stop switch.
* 3. All node addresses must be unique. The ERR light will illuminate when 0 or greater than 125 is entered.
23
Table 7 Parameter Settings
Name
Selects the frequency reference input source
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
*1
2: MEMOBUS communications
3: Option PCB
4: Pulse Input (Terminal RP)
Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S1 to S7
*1
2: MEMOBUS communications
3: Option PCB
Determines drive response when a bUS error is detected
during communications with the PROFIBUS-DP Option
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Sets the condition for external fault detection (EF0)
0: Always detected
1: Detected only during operation
Determines drive response for external fault input (EF0)
detection during PROFIBUS communication
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Set the maximum time the drive should wait for a
communication error to occur (bUS)
Range 0.00 to 5.00 s
0 to 125
*3
Selects the action to take when a "Clear Mode" command
is received
0: Resets back to 0
1: Maintains the previous value
0: PPO Type
1: Conventional
YASKAWA ELECTRIC TOBP C730600 23A V1000 Option PROFIBUS-DP Installation Manual
Table 7
before starting network
Description
*2
Default
1
1
1
0
1
0.05 s
0