YASKAWA SI-P3/V Installation Manual page 30

Ac drive-v1000 option
Hide thumbs Also See for SI-P3/V:
Table of Contents

Advertisement

LED Operator Display
Cause
Non-compatible option connected to
the drive.
LED Operator Display
Cause
Problem with the connectors between
the drive and PROFIBUS-DP Option.
LED Operator Display
Cause
PROFIBUS-DP Option hardware
fault.
LED Operator Display
Cause
PROFIBUS-DP Option hardware
fault.
YASKAWA ELECTRIC TOBP C730600 23A V1000 Option PROFIBUS-DP Installation Manual
Fault Name
PROFIBUS-DP Option Fault (Port A)
oFA00
PROFIBUS-DP Option is not properly connected.
Corrective Action
⇒ Connect an option that is compatible with the drive.
Fault Name
PROFIBUS-DP Option Fault (Port A)
oFA01
PROFIBUS-DP Option is not properly connected.
Corrective Action
⇒ Turn the power off and check the connectors between the drive and
PROFIBUS-DP Option.
Fault Name
PROFIBUS-DP Option Fault (Port A)
oFA03
PROFIBUS-DP Option self-diagnostics error.
Corrective Action
⇒ Replace the PROFIBUS-DP Option. Contact Yaskawa for assistance.
Fault Name
PROFIBUS-DP Option Fault (Port A)
oFA04
PROFIBUS-DP Option Flash write mode
Corrective Action
⇒ Replace the PROFIBUS-DP Option. Contact Yaskawa for assistance.
8 Troubleshooting
30