5: Pager/Modem Tab - Johnson Controls IFI-WS Installation And Operation Manual

Intelligent fire integrator
Table of Contents

Advertisement

Workstation Settings
4.2.5 Pager/Modem Tab
The Pager/Modem tab allows the user to configure the optional paging capabilities of the workstation. These settings
match the settings required for the specific pager. Settings are described in
Pager notifications are only intended to be transmitted to a limited number of staff for maintenance and system status
purposes. This feature is approved by UL as supplementary.
Setting
Buttons:
Add Pager
Delete Pager
Pager List: Click the fields below the headings to enter/modify text or select options from a drop-down list.
Pager
Phone
PIN
Enabled/Disabled
All Day
Start Time
Stop Time
Monitoring
Output
Sample Output: Displays a sample of the event message that will be sent to the selected pager using the format
configured above.
Modem: Displays settings for the connected modem.
Dialing Delay (Sec.)
Retry Delay (Sec.)
Number of Retries
Time Out (Sec.)
IFI-WS Installation and Operation Manual – P/N LS10050-000JC-E:A 12/11/2014
Table 4.6 Pager/Modem Tab Settings
Possible Settings
Click to display a pager name dialog box. Enter a unique pager
name and click Yes. The pager name is displayed in the pagers
list.
Highlight a pager name in the list and click to delete it.
Text Field
Automatically populates the pager name when a pager is added.
Text Field
Enter the pager phone number.
Text Field
Enter the pager PIN number.
Enabled
Enable the pager selected in the pager list field.
Disabled
Disable the pager selected in the pager list field.
Yes
Send the event message whenever it occurs.
No
Send the event message at configured start and stop times.
12 AM to 11 PM in
Activates only when "All Day>No" setting is selected. Select the
Hourly Increments
times from the drop-down list.
Default
Use the system default monitoring profile.
User-defined
Select a user-defined monitoring profile from the drop-down list.
Monitoring Profiles
Refer to
Default
Use the system default output format.
User-defined Output
Select a user-defined output format from the drop-down list.
Format
Refer to
10 to 30 seconds
The time the modem waits before dialing the pager phone
number after the event occurs. (Default is 10 seconds)
10 to 30 seconds
The time the modem waits before re-dialing the pager phone
number. (Default is 10 seconds)
0 to 3
The number of times the modem tries to send the message if it
fails. (Default is 2)
45 to 300 seconds
The maximum time the modem will spend trying to contact the
pager. (Default is 90 seconds)
Table
4.6.
Description
3.4, "Adding to an Existing
Network".
4.2.7, "Output
Tab".
Workstation Settings
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents