Compatible Equipment - Johnson Controls IFI-WS Installation And Operation Manual

Intelligent fire integrator
Table of Contents

Advertisement

Product Overview
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard
for Control Units and Accessories for Fire Alarm Systems, UL 2572 certain programming features or options must be limited to
Program feature or option
Inactivity Timeout

1.10 Compatible Equipment

The equipment listed in the table below is compatible with the IFI-WS:
Equipment
Monitors:
MON-22LCDW
MON-22LCDW-TS
MON-42LCDW
• Monitor electrical ratings: 120 VAC, 60 Hz 3.5 Amps for both models.
• To remain compliant with UL listing and to meet the "Condition of Acceptability", the keyboard and mouse must be
connected when using a touchscreen monitor.
• In Canada, all wiring connections to the monitor must be encased in conduit.
Gateways:
JNFN-GW-EM-3
JNFN-GW-PC-HNW
JNFN-GW-PC-HNSF
JNFN-GW-PC-HNMF
JNFN-GW-PC-W
JNFN-GW-PC-F
JDACR-GW
JLEDSIGN-GW
Misc:
JNOTIFY-IP
16
Table 1.6 UL 2572 Field-programmable Settings
specific values or not used at all as indicated below.
Permitted in UL 2572
(Y/N)
Yes
Table 1.7 Compatible Equipment
22" Wide screen LCD Monitor
Touchscreen 22" Wide screen LCD Monitor
Touchscreen 42" Wide screen LCD Monitor
Embedded NFN Gateway
NFN PC Gateway card (wire connections)
NFN PC Gateway card (single mode fiber connections)
NFN PC Gateway card (multi mode fiber connections)
NFN PC Gateway card (wire connections)
NFN PC Gateway card (fiber connections)
Digital Alarm Communicator Receiver Gateway
LEDSIGN Gateway
Text
Notify IP
IFI-WS Installation and Operation Manual – P/N LS10050-000JC-E:A 12/11/2014
Possible Settings
0 - 20 minutes (0 disables
feature)
Description
Compatible Equipment
Settings permitted in UL 2572
1 - 20 minutes

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents