Agency Listings

1.6.3 IP Restrictions
The following restrictions apply:
• Workstations cannot access gateways or other workstations through Network Address Translation or
IP Masquerading.
• Must have a static IP address. DHCP is not supported.
• Multiple IP Addresses are not supported, either due to multiple enabled network adapters or due to a
multi-homed adapter.
• The optional email server must support sending email without authentication.
1.7 Agency Listings
1.7.1 Standards
Compliance - This product has been investigated to, and found to be in compliance with, the
following standards:
National Fire Protection Association
• NFPA 72
Underwriters Laboratories
• UL 864
• UL 1076
• UL 2017
• UL 2572
Underwriters Laboratories Canada
• CAN/ULC S527-99 Standard for Control Units for Fire Alarm Systems, Second Edition
• CAN/ULC S559-04 Equipment for Fire Signal Receiving Centres and Systems, First Edition
Installation - This product is intended to be installed in accordance with the following:
Local
• AHJ
National Fire Protection Association
• NFPA 70
• NFPA 72
Underwriters Laboratories
• UL 1076
Underwriters Laboratories Canada
• CAN/ULC S524-06 Installation of Fire Alarm Systems
• CAN/ULC S561-03 Installation and Services for Fire Signal Receiving Centers and Systems
IFI-WS Installation and Operation Manual – P/N LS10050-000JC-E:A 12/11/2014
National Fire Alarm Code
Control Units for Fire Alarm Systems, Ninth Edition
Proprietary Burglar Alarm Units and Systems, Fifth Edition
General-Purpose Signaling Devices and Systems, First Edition
Mass Notification Systems, First Edition
Authority Having Jurisdiction
National Electrical Code
National Fire Alarm Code
Proprietary Burglar Alarm Units and Systems, Fifth Edition
Product Overview