Wiring Configuration For Automatic Motor Adaptation (Ama) Without T27; Wiring Configuration: Speed - Danfoss VLT HVAC Drive FC 102 Operating Manual

110-800 kw, enclosures d9h-d10h and e5h-e6h
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Operating Guide | VLT® HVAC Drive FC 102

8.1.2 Wiring Configuration for Automatic Motor Adaptation (AMA) without T27

Table 50: Wiring Configuration for AMA without T27 Connected
+24 V
XD2.10
+24 V
XD2.11
D IN
XD2.12
D IN
XD2.13
COM
XD2.18
XD2.14
D IN
D IN
XD2.15
XD2.16
D IN
D IN
XD2.17
D IN
XD2.19
+10 V
XD2.6
A IN
XD2.7
A IN
XD2.8
COM
XD2.9
A OUT
XD2.5
COM
XD2.4

8.1.3 Wiring Configuration: Speed

Table 51: Wiring Configuration for Analog Speed Reference (Voltage)
+10 V
XD2.6
+
A IN
XD2.7
A IN
XD2.8
COM
XD2.9
-
A OUT
XD2.5
0–10 V
COM
XD2.4
U - I
A53
110 | Danfoss A/S © 2018.10
Parameters
Function
Parameter 1-29 Automatic Motor Adaptation (AMA)
Parameter 5-12 Terminal 27 Digital Input
*=Default value
Notes/comments:
Set parameter group 1-2* Motor Data according to motor nameplate.
Terminal 27 in the parameter title corresponds to terminal XD2.14 in the control compartment.
Parameters
Function
Parameter 6-10 Terminal 53 Low Voltage
Parameter 6-11 Terminal 53 High Voltage
Parameter 6-14 Terminal 53 Low Ref./Feedb. value
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
*=Default value
Notes/comments:
D IN 37 is an option.
Terminal 53 in the parameter title corresponds to terminal XD2.7 in the control compartment.
Wiring Configuration Examples
Setting
[1] Enable complete AMA
[0] No operation
Setting
0.07 V*
10 V*
0 Hz
50 Hz
AQ262141314214en-000101 / 130R0880