CHAPTER 5: WinESG
 
Soft starter time:
Soft stop time:
Under current delay time:
Start attempts time:
5.3.2.6 Parameterization Counter panel
The counter panel provides a means for setting two parameterizable counters: Counter 1 and Counter 2. They are
selectable from 0 to 65535 in steps of 1. Details are available in logic documentation. Counter 3 is used for Start
attempt counter, and it is settable from 1 to 40. This is the number of start attempts allowed within a specified timer
(Start attempts time). Refer to Figure 5-12 for the WinESG parameterization counter panel.
Figure 5-12-: WinESG parameterization counter panel
5.3.2.7 Parameterization Control panel
The control panel provides a means for setting the controls of the local/remote switch, the remote and local devices
and the device behavior In case of fault. Refer to figure 5-13 for the WinESG parameterization control panel.
5.21
 
use on soft starter typical. Transition to by-pass will occur after
this time expires.
use on soft starter typical. Transition from by-pass to soft starter
stop control will occur after this time expires.
fault or warning is indicated if a current is below under current
threshold for the set amount of time.
indicates the allowable time to make the number of start
attempts set in start attempt counter (Counter 3).
EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL