If the default configuration and the DOL reverse typical are selected in the WinESG parameterization/information shown
in the illustration below or by setting Modbus function code 6 register 62 bit0 to 1 and bits 8,9,10 and 11 to 0x1,the
inputs and outputs are mapped as below:
For EntelliPro ES3 types:
Input 99 is mapped to contactor 1 feedback
Input 98 is mapped to contactor 2 feedback
Input 97 is mapped to control circuit feedback
Input 96 is mapped to main circuit feedback
Input 95 is mapped to emergency stop
Input 94 is mapped to external supervision
Input 93 is mapped to safety circuit
Output 41 is mapped to contactor 1
Output 43 is mapped to contactor 2
Output 45 is mapped to failure
For EntelliPro ES5 types:
Input 99 is mapped to contactor 1 feedback
Input 98 is mapped to contactor 2 feedback
Input 97 is mapped to reset alarm
Input 96 is mapped to drawer in test mode
Input 95 is mapped to drawer in operation mode
Input 94 is mapped to main circuit feedback
Input 93 is mapped to control circuit
Input 11 is mapped to command OFF
Input 12 is mapped to command ON1
Input 13 is mapped to command ON2
Input 14 is mapped to external fault
Input 15 is mapped to external supervision
Input 16 is mapped to emergency stop
Input 17 is mapped to safety circuit
Input 18 is mapped to mode switch local
Input 19 is mapped to mode switch remote
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
CHAPTER 2: INSTALL ATION/CONFIGURATION
- active high
- active high
- active low
- active low
- active low
- active high
- active low
- active high
- active high
- active high
- active high
- active high
- active low
- active low
- active low
- active high
- active high
- active high
- active low
- active low
- active low
- active high
- active high
2.28